Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
Base efficiency Heat Pump rooftop unit available with field and factory installed accessories for easy installation and serviciability.
Unit of Measure

Cooling Capacity

N/A 46000 Btu/h4 TR

IEER

N/A 14.0

EER

N/A 11.5

Heating Capacity

N/A 45500 Btu/h

HSPF

N/A 8

COP

N/A 2.34

Sound Level

N/A 73.0 dB

Operating Weight

N/A 642 lb

Shipping Weight

N/A 688 lb

Motor Type

N/A Belt Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 12 x 11 in

Indoor Nominal CFM

N/A 1460

Evaporator Motor - RPM

N/A 1725

Evaporator Motor Horsepower

N/A 1.0 hp

Filter Size

N/A 14 x 20 x 2 (4) in

Drain Size (NPT)

N/A 3/4 in

R410A Refrigerant Charge

N/A 195 oz

Evaporator Coil Face Area

N/A 7.3 ft²

Rows Deep

N/A 4

Fins per Inch

N/A 16

Motor Sheave

N/A 1VL40 X 5/8

Blower Sheave

N/A AK66H

Belt

N/A AX52

Outdoor Horsepower

N/A 1

RPM (High/Low stage)

N/A 1075

Outdoor Horsepower

N/A 1/4 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 4

Condenser Coil Face Area

N/A 17.3 ft²

Rows Deep

N/A 2

Fins per Inch

N/A 16

Quantity

N/A 1

Type

N/A Scroll

Stage

N/A 1

Rated Load Amps

N/A 4.36 A

Locked Rotor Amps

N/A 33 A

Voltage

N/A 575 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 2.3 A

Max External Static

N/A 0.7 inWc

Outdoor Fan FLA

N/A 0.55 A

Min. Circuit Ampacity

N/A 8.3 A

Max. Overcurrent Protection

N/A 15 A

Power Supply Conduit Hole Diameter

N/A 1.125 in

Low-Voltage Conduit Hole Diameter

N/A 0.5 in

Depth

N/A 74 in

Width

N/A 48-5/16 in

Height

N/A 39-7/8 in

N/A

  • Capacity Range from 3 to 5 tons
  • Belt and Direct Drive Available
  • Single phase power available

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.