Gas/Electric
- Capacity range from 3 to 12.5 tons
- Numerous voltages and phases for application flexibility
- All units has a choice of 3-phase 208/230V, 460V or 575V
- 3-5 ton units also have a choice of 1-phase 208/230V
- All models have ECM Direct-Drive Indoor Fan Motor
- Designed to fit standard curb sizes for ease of many replacements
Unit of Measure
Items |
DRG0361DL00001S Light Commercial Rooftop |
DRG0361DM00001S Light Commercial Rooftop |
DRG0361DH00001S Light Commercial Rooftop |
DRG0363DL00001S Light Commercial Rooftop |
DRG0363DM00001S Light Commercial Rooftop |
|||||
Nominal Capacity | N/A 3.0 TR | |||||||||
Cooling Capacity | N/A 36000 Btu/h | |||||||||
Heating Capacity | N/A 46000 / 37300 Btu/h | N/A 70000 / 56700 Btu/h | N/A 115000 / 93200 Btu/h | N/A 46000 / 37300 Btu/h | N/A 70000 / 56700 Btu/h | |||||
SEER | N/A 17.1 | |||||||||
IEER | N/A | |||||||||
EER | N/A 13.0 | |||||||||
Height | N/A 39-7/8 in | |||||||||
Width | N/A 48-5/16 in | |||||||||
Depth | N/A 74 in | |||||||||
Heat Range | N/A Low | N/A Medium | N/A High | N/A Low | N/A Medium | |||||
No. of Burners | N/A 2 | N/A 3 | N/A 6 | N/A 2 | N/A 3 | |||||
Thermal Efficiency (T.E.) | N/A | N/A | N/A | N/A 81 | N/A 81 | |||||
Annual Fuel Utilization Efficiency (AFUE) | N/A 81 | N/A 81 | N/A 81 | N/A | N/A | |||||
High Stage Temperature Rise Range | N/A 15 to 45 ºF | N/A 25 to 55 ºF | N/A 45 to 75 ºF | N/A 15 to 45 ºF | N/A 25 to 55 ºF | |||||
Low Stage Temperature Rise Range | N/A 5 to 35 ºF | N/A 15 to 45 ºF | N/A 34 to 65 ºF | N/A 5 to 35 ºF | N/A 15 to 45 ºF | |||||
Evaporator Motor Type | N/A Direct Drive | |||||||||
External Static Pressure (ESP) | N/A Standard | |||||||||
Evaporator Motor / Coil - Wheel Dia. x Width | N/A 12 x 11 in | |||||||||
Evaporator Motor / Coil - Indoor Nominal CFM | N/A 1200 | |||||||||
Evaporator Motor - RPM | N/A 1200 | |||||||||
Evaporator Motor Horsepower | N/A 3/4 hp | |||||||||
Evaporator Motor / Coil - Filter Size | N/A 14 x 20 x 2 (4) in | |||||||||
Evaporator Motor / Coil - Drain Size (NPT) | N/A 3/4 in | |||||||||
Evaporator Motor / Coil - R410A Refrigerant Charge | N/A 96 oz | |||||||||
Evaporator Coil - Face Area | N/A 7.3 ft² | |||||||||
Evaporator Coil - Rows Deep | N/A 4 | |||||||||
Evaporator Coil - Fins per Inch | N/A 16 | |||||||||
Quantity of Condenser Fan Motors | N/A 1 | |||||||||
Condenser Fan - RPM (High/Low stage) | N/A 810 | |||||||||
Condenser Fan - Outdoor Horsepower | N/A 0.17 hp | |||||||||
Condenser Fan Diameter | N/A 22 in | |||||||||
Condenser Fan - No. of Fan Blades | N/A 3 | |||||||||
Condenser Coil - Face Area | N/A 12.5 ft² | |||||||||
Condenser Coil - Rows Deep | N/A 2 | |||||||||
Condenser Coil - Fins per Inch | N/A 28 | |||||||||
Compressor Quantity | N/A 1 | |||||||||
Compressor Type | N/A Scroll | |||||||||
Compressor Stage | N/A 2 | |||||||||
Compressor Rated Load Amps | N/A 15.3 A | N/A 15.3 A | N/A 15.3 A | N/A 11.6 A | N/A 11.6 A | |||||
Compressor Locked Rotor Amps | N/A 83 A | N/A 83 A | N/A 83 A | N/A 73 A | N/A 73 A | |||||
Voltage | N/A 208 to 230 V | |||||||||
Number of Phases | N/A 1 | N/A 1 | N/A 1 | N/A 3 | N/A 3 | |||||
Frequency | N/A 60 Hz | |||||||||
Indoor Blower FLA | N/A 5.7 A | |||||||||
Max External Static | N/A 1 inWc | |||||||||
Outdoor Fan FLA | N/A 0.95 A | |||||||||
Min. Circuit Ampacity | N/A 25.7 / 25.7 A | N/A 25.7 / 25.7 A | N/A 25.7 / 25.7 A | N/A 21.2 / 21.2 A | N/A 21.2 / 21.2 A | |||||
Max. Overcurrent Protection | N/A 40 /40 A | N/A 40 /40 A | N/A 40 /40 A | N/A 30 / 30 A | N/A 30 / 30 A | |||||
Power Supply Conduit Hole Diameter | N/A 1.125 in | |||||||||
Low-Voltage Conduit Hole Diameter | N/A 0.5 in | |||||||||
Operating Weight | N/A 572 lb | |||||||||
Shipping Weight | N/A 630 lb | |||||||||
|