Light Commercial
Unit of Measure
Items
DFH 3-6 ton - DFC image shown

3 Ton Heat Pump Direct Drive Single Phase 208-230V

DFH 3-6 ton - DFC image shown

3 Ton Heat Pump Direct Drive 3 Phase 208-230V

DFH 3-6 ton - DFC image shown

3 Ton Heat Pump Direct Drive 3 Phase 460V

DFH 3-6 ton - DFC image shown

3 Ton Heat Pump Direct Drive 3 Phase 575V

DFH 3-6 ton - DFC image shown

4 Ton Heat Pump Direct Drive Single Phase 208-230V
Type N/A Light Commercial Packaged Heat Pump
Cooling Capacity N/A 35000 Btu/h3 T N/A 35000 Btu/h3 T N/A 35000 Btu/h3 T N/A 35000 Btu/h3 T N/A 46000 Btu/h4 T
IEER N/A
System Performance SEER N/A
System Performance EER N/A
System Performance SEER2 N/A 13.4
System Performance EER2 N/A 11.0
AHRI Reference # N/A 210643306 N/A 210643303 N/A 210643304 N/A 210643305 N/A 210643302
Sound Level N/A 74 dB N/A 74 dB N/A 74 dB N/A 74 dB N/A 79 dB
Heating Capacity N/A 33600 Btu/h N/A 33600 Btu/h N/A 33600 Btu/h N/A 33600 Btu/h N/A 46000 Btu/h
HSPF2 N/A 6.70
COP at 47F / COP at 17F N/A
Evaporator Motor Type N/A
External Static Pressure (ESP) N/A Standard
Evaporator Motor / Coil - Wheel Dia. x Width N/A 12 x 11 in
Evaporator Motor / Coil - Indoor Nominal CFM N/A 1170 N/A 1170 N/A 1170 N/A 1170 N/A 1600
Evaporator Motor - RPM N/A 1200/VAR N/A 1200/VAR N/A 300-1500 N/A 300-1500 N/A 1200/VAR
Evaporator Motor Horsepower N/A 3/4 hp N/A 3/4 hp N/A 1.2 hp N/A 1.2 hp N/A 1.0 hp
Evaporator Motor / Coil - Filter Size N/A 14 x 20 x 2 (4) in
Evaporator Motor / Coil - Drain Size (NPT) N/A 3/4 in
Evaporator Motor / Coil - R-410A Refrigerant Charge N/A 165 oz N/A 165 oz N/A 165 oz N/A 165 oz N/A 212 oz
Evaporator Coil Face Area N/A 7.33 ft²
Evaporator Coil - Rows Deep N/A 3 N/A 3 N/A 3 N/A 3 N/A 4
Evaporator Coil - Fins per Inch N/A 16
Quantity of Condenser Fan Motors N/A 1
Condenser Fan - RPM (High/Low stage) N/A 810 N/A 810 N/A 810 N/A 810 N/A 1075
Condenser Fan - Outdoor Horsepower N/A 1/6 hp N/A 1/6 hp N/A 1/6 hp N/A 1/6 hp N/A 1/4 hp
Condenser Fan Diameter N/A 22 in
Condenser Fan - No. of Fan Blades N/A 3 N/A 3 N/A 3 N/A 3 N/A 4
Condenser Coil Face Area N/A 12.67 ft² N/A 12.67 ft² N/A 12.67 ft² N/A 12.67 ft² N/A 17.28 ft²
Condenser Coil - Rows Deep N/A 2
Condenser Coil - Fins per Inch N/A 16
Compressor Type N/A Scroll
Compressor Quantity N/A 1
Compressor Stage N/A 1
Compressor Rated Load Amps N/A 16.7 A N/A 10.4 A N/A 5.8 A N/A 3.8 A N/A 19.9 A
Compressor Locked Rotor Amps N/A 79 A N/A 73 A N/A 38 A N/A 36.5 A N/A 109 A
Voltage N/A 208 to 230 V N/A 208 to 230 V N/A 460 V N/A 575 V N/A 208 to 230 V
Number of Phases N/A 1 N/A 3 N/A 3 N/A 3 N/A 1
Frequency N/A 60 Hz
Indoor Blower FLA N/A 5.7 A N/A 5.7 A N/A 2.5 A N/A 2 A N/A 6.9 A
Max External Static N/A 0.8 inWc
Outdoor Fan FLA N/A 0.95 A N/A 0.95 A N/A 0.48 A N/A 0.39 A N/A 1.4 A
Min. Circuit Ampacity N/A 27.5/27.5 A N/A 19.7/19.7 A N/A 10.2 A N/A 7.1 A N/A 33.1/33.1 A
Max. Overcurrent Protection N/A 40/40 A N/A 30/30 A N/A 15 A N/A 15 A N/A 50/50 A
Power Supply Conduit Hole Diameter N/A 1.125 in
Low-Voltage Conduit Hole Diameter N/A 0.5 in
Depth N/A 74 in
Width N/A 48-5/16 in
Height N/A 39-7/8 in
Operating Weight N/A 536 lb N/A 535 lb N/A 543 lb N/A 543 lb N/A 587 lb
Shipping Weight N/A 606 lb N/A 605 lb N/A 613 lb N/A 613 lb N/A 657 lb
Features N/A Installation
Daikin Packaged units are designed with fast and easy installation in mind and are ideal for both new construction and retrofit projects. Our packaged rooftop units are built to be a direct replacement for most rooftop units in the field without the need of a curb adapter, to be able to replace the unit in a shorter time and at a lower cost.

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors to match the required total load.

Supply Fan
The direct-drive airfoil single width, single inlet (SWSI) Class II construction supply fan with aluminum fan blades provides efficient and quiet operation at wide ranging static pressure and air flow requirements.

Coils
All units use large face area outdoor coils. These coils are constructed with seamless copper tubes, mechanically bonded into aluminum plate-type fins with full drawn collars to completely cover the tubes for high operating efficiencies.

Heat Pump Heating
Evaporator coil, condenser coil, compressors and refrigerant circuit are designed for heat pump operation.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use weatherproof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and long lasting component maintenance.

Heating Section
Wide ranging of electric heat selections effectively handle most comfort heating demand from morning warm-up control to full heat.

Electric Heat
ETL approved electric heat is factory assembled, installed and tested.

Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.