Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
VRV-IV Water Cooled Heat Pump - RWEYQ Series
VRV Water Cooled Heat Pump
All the benefits of VRV in a water cooled design.
VRV IV W-Series systems are equivalent to 4-pipe chilled water systems, but also offer a viable alternative to Water Source Heat Pump solutions. Each connected indoor unit can provide heating and cooling independently to suit zone requirements making these systems suitable for both open plan, or cellular applications with different operation requirements.
- VRV with Variable Refrigerant Temperature (VRT) technology Capacity range from 6 to 21 tons
- 208-230V / 3ph / 60Hz (RWEYQ_PCTJ)
- 460V / 3ph / 60Hz (RWEYQ_PCYD)
Unit of Measure
Items |
RWEYQ72PCTJ VRV-IV Water Cooled Heat Pump - RWEYQ Series |
RWEYQ84PCTJ VRV-IV Water Cooled Heat Pump - RWEYQ Series |
RWEYQ144PCTJ VRV-IV Water Cooled Heat Pump - RWEYQ Series |
RWEYQ168PCTJ VRV-IV Water Cooled Heat Pump - RWEYQ Series |
RWEYQ216PCTJ VRV-IV Water Cooled Heat Pump - RWEYQ Series |
|||||
Model Type | N/A Heat Pump | |||||||||
Heat Exchanger Type | N/A Stainless Steel Plate | |||||||||
Color | N/A Ivory White (5Y7.5/1) | |||||||||
Cooling Capacity | N/A 72000 Btu/h | N/A 84000 Btu/h | N/A 144000 Btu/h | N/A 168000 Btu/h | N/A 216000 Btu/h | |||||
Heating Capacity | N/A 81000 Btu/h23.7 kW | N/A 94000 Btu/h27.5 kW | N/A 162000 Btu/h47.5 kW | N/A 189000 Btu/h55.4 kW | N/A 243000 Btu/h71.2 kW | |||||
Power Supply | N/A 208/230 V, 60 Hz, 3 phase | |||||||||
Voltage | N/A 208/230 V | |||||||||
Frequency | N/A 60 Hz | |||||||||
Height | N/A 39-3/8 in1000 mm | N/A 39-3/8 in1000 mm | N/A (39-3/8) x 2 in(1000) x 2 mm | N/A (39-3/8) x 2 in(1000) x 2 mm | N/A (39-3/8) x 3 in(1000) x 3 mm | |||||
Width | N/A 30-3/4 in780 mm | N/A 30-3/4 in780 mm | N/A (30-3/4) x 2 in(780) x 2 mm | N/A (30-3/4) x 2 in(780) x 2 mm | N/A (30-3/4) x 3 in(780) x 3 mm | |||||
Depth | N/A 21-11/16 in550 mm | N/A 21-11/16 in550 mm | N/A (21-11/16) x 2 in(550) x 2 mm | N/A (21-11/16) x 2 in(550) x 2 mm | N/A (21-11/16) x 3 in(550) x 3 mm | |||||
Compressor Type | N/A Hermetically Sealed Scroll | |||||||||
Compressor Displacement | N/A 395 ft³/h | N/A 482 ft³/h | N/A 395 x 2 ft³/h | N/A 482 x 2 ft³/h | N/A 395 x 3 ft³/h | |||||
Compressor Number of Revolutions | N/A 5280 rpm | N/A 6450 rpm | N/A 5280 x 2 rpm | N/A 6450 x 2 rpm | N/A 5280 x 3 rpm | |||||
Compressor Motor Output x Number of Units | N/A 3.6 x 1 kW | N/A 4.0 x 1 kW | N/A 3.6 x 2 kW | N/A 4.0 x 2 kW | N/A 3.6 x 3 kW | |||||
Compressor Starting Method | N/A Soft Start | |||||||||
Pipe Connections - Gas | N/A 19.1 mm | N/A 22.2 mm | N/A 28.6 mm | N/A 28.6 mm | N/A 34.9 mm | |||||
Pipe Connections - Water Inlet | N/A 1-1/4 FPT Female Thread | |||||||||
Pipe Connections - Water Outlet | N/A 1-1/4 FPT Female Thread | |||||||||
Safety Devices | N/A High Pressure Switch, Inverter Overload Protector, Fusible Plug | |||||||||
Capacity Control | N/A 23 to 100 % | N/A 23 to 100 % | N/A 11 to 100 % | N/A 11 to 100 % | N/A 8 to 100 % | |||||
System Performance IEER | N/A 22.30 | N/A 21.30 | N/A 22.30 | N/A 21.30 | N/A 20.90 | |||||
System Performance IEER Non-Ducted | N/A 24.10 | N/A 22.50 | N/A 23.7 | N/A 23.10 | N/A 22.20 | |||||
System Performance Heating COP | N/A 4.8 | N/A 4.5 | N/A 5.0 | N/A 4.4 | N/A 4.9 | |||||
System Performance Heating COP Non-Ducted | N/A 4.9 | N/A 4.7 | N/A 5.0 | N/A 4.4 | N/A 4.8 | |||||
Weight | N/A 150 kg330 lb | N/A 150 kg330 lb | N/A 150 + 150 kg330 + 330 lb | N/A 150 + 150 kg330 + 330 lb | N/A 150 + 150 + 150 kg330 + 330 + 330 lb | |||||
Standard Accessories | N/A Installation Manual, Operation Manual, Connection Pipes, Clamps, Conduit Mounting Plate | |||||||||
|
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.