Light Commercial Rooftop packaged unit cooling only
Daikin Packaged units are designed with an easier and faster installation in mind for both new construction and retrofit. Built for comfort cooling applications in normal heating, ventilating, and air conditioning. Designed on a variety of fuels such AC only, Gas Electric and Heat Pump to fit on most types of applications, at different static and efficiency requirements.
Capacity Range from 3 to 5 tons features:
Daikin Packaged units are designed with an easier and faster installation in mind for both new construction and retrofit. Built for comfort cooling applications in normal heating, ventilating, and air conditioning. Designed on a variety of fuels such AC only, Gas Electric and Heat Pump to fit on most types of applications, at different static and efficiency requirements.
Capacity Range from 3 to 5 tons features:
- Belt and Direct Drive Available -
- Single phase power available
- 208-230, 460 and 575v available
- Belt Drive flexibility
- Two stage capacity for partial load
- Belt Drive flexibility
- Two stage capacity for partial load
Unit of Measure
- Specifications
- Evaporator Motor / Coil
- Condenser Fan / Coil
- Compressor
- Electrical Data
- Dimensions
- Features
Model Type |
N/A Air Conditioner Units |
Cooling Capacity |
N/A 69000 Btu/h6 TR |
System Performance EER |
N/A 11.2 |
System Performance IEER |
N/A 15.0 |
Sound Level |
N/A 81 dBA |
Operating Weight |
N/A 678 lb |
Shipping Weight |
N/A 724 lb |
Motor Type |
N/A 2 Speed Belt Drive |
External Static Pressure (ESP) |
N/A Standard |
Wheel Dia. x Width |
N/A 12 x 10 in |
Indoor Nominal CFM |
N/A 2130 |
Evaporator Motor - RPM |
N/A 1740 |
Evaporator Motor Horsepower |
N/A 2.00 hp |
Filter Size |
N/A 14 x 20 x 2 (2) in20 x 20 x 2 (2) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 154 oz |
Evaporator Coil - Face Area |
N/A 9.2 ft² |
Evaporator Coil - Rows Deep |
N/A 4 |
Evaporator Coil - Fins per Inch |
N/A 16 |
Quantity of Condenser Fan Motors |
N/A 1 |
RPM (High/Low stage) |
N/A 1050 |
Outdoor Horsepower |
N/A 0.33 hp |
Diameter |
N/A 22 in |
No. of Fan Blades |
N/A 4 |
Condenser Coil Face Area |
N/A 19.0 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 28 |
Quantity |
N/A 1 |
Type |
N/A Scroll |
Stage |
N/A 2 |
Rated Load Amps |
N/A 8.5 A |
Locked Rotor Amps |
N/A 66.1 A |
Voltage |
N/A 460 V |
Phase |
N/A 3 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 2.9 A |
Max External Static |
N/A 1.8 inWc |
Outdoor Fan FLA |
N/A 0.85 A |
Min. Circuit Ampacity |
N/A 14.3 A |
Max. Overcurrent Protection |
N/A 20 A |
Power Supply Conduit Hole Diameter |
N/A 1.125 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.5 in |
Depth |
N/A 74 in |
Width |
N/A 48-5/16 in |
Height |
N/A 43 1/2 in |