Model Type

N/A Belt Drive

Indoor Airflow

N/A 4000 ft³/min

Blower Motor Power

N/A 2 hp

Frequency

N/A 60 Hz

Voltage

N/A 460 V

Cooling Capacity

N/A 120000 Btu/h

Optional Electric Heating Capacity

N/A 15 kW20 kW30 kW

Phase

N/A 3

Minimum Circuit Ampacity

N/A 3.63 A

Transformer

N/A Standard

Blower Relay

N/A Standard

Disposable Filter Size

N/A 16x20x2(2) in20x20x2(2) in

Coil Area

N/A 10 ft²

FPI - Rows

N/A 14-4

Expansion Valve No.

N/A 2

Refrigerant

N/A R-410A

Depth

N/A 48 1/8 in

Width

N/A 24 in

Height

N/A 60 1/2 in

Liquid Connection diameter and Qty

N/A 3/8 (2) in

Suction Connection diameter and Qty

N/A 1 1/8 (2) in

Condensate Drain

N/A 3/4 FPT in

N/A Standard Features

  • Upflow or horizontal (left side) installation positions in 7½- and 10-ton coolingonly or heat pump applications
  • 10-ton DAT model circuited for use with two 5-ton cooling-only or heat pump systems; 7½-ton DAT model circuited for use with two 4-ton cooling-only or heat pump systems
  • Transformer and blower relay
  • TXV control; DAT units have two (2) expansion valves
  • Draw-thru centrifugal blower is beltdriven for quiet, efficient operation
  • Copper tube/aluminum fin coils
Cabinet Features
  • Heavy-gauge galvanized-steel cabinet
  • Fully insulated with fiberglass blanket
  • Horizontal and vertical condensate pans
  • Built-in filter rack (2” filter included)
  • Entry on top of panel for both low and high voltage
  • Removable access panels make servicing of unit faster and easier