Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
Base efficiency Gas/Electric rooftop unit available with field and factory installed accessories for easy installation and serviciability.
Unit of Measure

Model Type

N/A Gas/Electric Unit

Nominal Heating Capacity

N/A 210000 Btu/h

Cooling Capacity

N/A 114000 Btu/h10 TR

System Performance EER

N/A 11

System Performance IEER

N/A 12.7

Sound Level

N/A 82 dBA

Heat Range

N/A High

No. of Burners

N/A 7

High Stage Input

N/A 210 Btu/h

High Stage Output

N/A 168 Btu/h

Low Stage Input

N/A 157 Btu/h

Low Stage Output

N/A 126 Btu/h

Thermal Efficiency (T.E.)

N/A 80

High Stage Temperature Rise Range

N/A 25 to 55 ºF

Low Stage Temperature Rise Range

N/A 15 to 45 ºF

Operating Weight

N/A 1150 lb

Shipping Weight

N/A 1230 lb

Motor Type

N/A Belt Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 15 x 15 in

Indoor Nominal CFM

N/A 3600

Evaporator Motor - RPM

N/A 1740

Evaporator Motor Horsepower

N/A 2.00 hp

Filter Size

N/A 20 x 20 x 2 (4) in

Drain Size (NPT)

N/A 3/4 in

R410A Refrigerant Charge

N/A 103.5/103 oz

Evaporator Coil - Face Area

N/A 11 ft²

Evaporator Coil - Rows Deep

N/A 4

Evaporator Coil - Fins per Inch

N/A 16

Quantity of Condenser Fan Motors

N/A 2

RPM (High/Low stage)

N/A 1050

Outdoor Horsepower

N/A 0.33 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 31.3 ft²

Rows Deep

N/A 2

Fins per Inch

N/A 28

Quantity

N/A 2

Type

N/A Scroll

Stage

N/A 1

Rated Load Amps

N/A 7.8 A

Locked Rotor Amps

N/A 52.0 A

Voltage

N/A 460 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 2.9 A

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 0.85 A

Min. Circuit Ampacity

N/A 22.1 A

Max. Overcurrent Protection

N/A 25 A

Power Supply Conduit Hole Diameter

N/A 1.375 in

Low-Voltage Conduit Hole Diameter

N/A 0.375 in

Depth

N/A 93-3/4 in

Width

N/A 60-3/8 in

Height

N/A 54-9/10 in

N/A

  • Heat exchanger with wrinkle bend tech
  • Belt Drive flexibility
  • Two stage capacity for partial load

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.