Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
Base efficiency Gas/Electric rooftop unit available with field and factory installed accessories for easy installation and serviciability.
Unit of Measure
- Specifications
- Evaporator Motor / Coil
- Condenser Fan / Coil
- Compressor
- Electrical Data
- Dimensions
- Features
Model Type |
N/A Gas/Electric Unit |
Nominal Heating Capacity |
N/A 210000 Btu/h |
Cooling Capacity |
N/A 114000 Btu/h10 TR |
System Performance EER |
N/A 11 |
System Performance IEER |
N/A 12.7 |
Sound Level |
N/A 82 dBA |
Heat Range |
N/A High |
No. of Burners |
N/A 7 |
High Stage Input |
N/A 210 Btu/h |
High Stage Output |
N/A 168 Btu/h |
Low Stage Input |
N/A 157 Btu/h |
Low Stage Output |
N/A 126 Btu/h |
Thermal Efficiency (T.E.) |
N/A 80 |
High Stage Temperature Rise Range |
N/A 25 to 55 ºF |
Low Stage Temperature Rise Range |
N/A 15 to 45 ºF |
Operating Weight |
N/A 1150 lb |
Shipping Weight |
N/A 1230 lb |
Motor Type |
N/A Belt Drive |
External Static Pressure (ESP) |
N/A Standard |
Wheel Dia. x Width |
N/A 15 x 15 in |
Indoor Nominal CFM |
N/A 3600 |
Evaporator Motor - RPM |
N/A 1745 |
Evaporator Motor Horsepower |
N/A 2.00 hp |
Filter Size |
N/A 20 x 20 x 2 (4) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 103.5/103 oz |
Evaporator Coil - Face Area |
N/A 11 ft² |
Evaporator Coil - Rows Deep |
N/A 4 |
Evaporator Coil - Fins per Inch |
N/A 16 |
Quantity of Condenser Fan Motors |
N/A 2 |
RPM (High/Low stage) |
N/A 1050 |
Outdoor Horsepower |
N/A 0.33 hp |
Diameter |
N/A 22 in |
No. of Fan Blades |
N/A 3 |
Condenser Coil Face Area |
N/A 31.3 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 28 |
Quantity |
N/A 2 |
Type |
N/A Scroll |
Stage |
N/A 1 |
Rated Load Amps |
N/A 5.7 A |
Locked Rotor Amps |
N/A 38.9 A |
Voltage |
N/A 575 V |
Number of Phases |
N/A 3 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 2.4 A |
Max External Static |
N/A 0.8 inWc |
Outdoor Fan FLA |
N/A 0.67 A |
Min. Circuit Ampacity |
N/A 16.6 A |
Max. Overcurrent Protection |
N/A 20 A |
Power Supply Conduit Hole Diameter |
N/A 1.375 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.375 in |
Depth |
N/A 93-3/4 in |
Width |
N/A 60-3/8 in |
Height |
N/A 54-9/10 in |
N/A
|
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.