5 Ton Heat Pump Direct Drive 3 Phase 575V
Unit of Measure

Type

N/A Light Commercial Packaged Heat Pump

Cooling Capacity

N/A 58000 Btu/h5 T

System Performance SEER2

N/A 13.4

System Performance EER2

N/A 11.0

AHRI Reference #

N/A 210643297

Sound Level

N/A 79 dB

Operating Weight

N/A 600 lb

Shipping Weight

N/A 670 lb

Heating Capacity

N/A 55000 Btu/h

HSPF2

N/A 6.70

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 12 x 11 in

Indoor Nominal CFM

N/A 1840

RPM

N/A 300-1500

Evaporator Motor Horsepower

N/A 1.2 hp

Filter Size

N/A 14 x 20 x 2 (4) in

Drain Size (NPT)

N/A 3/4 in

R-410A Refrigerant Charge

N/A 207 oz

Evaporator Coil Face Area

N/A 7.33 ft²

Rows Deep

N/A 4

Fins per Inch

N/A 16

Quantity of Condenser Fan Motors

N/A 1

RPM (High/Low stage)

N/A 1050

Outdoor Horsepower

N/A 1/3 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 17.28 ft²

Rows Deep

N/A 2

Fins per Inch

N/A 20

Quantity

N/A Scroll

Type

N/A 1

Stage

N/A 1

Rated Load Amps

N/A 5.7 A

Locked Rotor Amps

N/A 38.9 A

Voltage

N/A 575 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 2 A

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 0.67 A

Min. Circuit Ampacity

N/A 9.8 A

Max. Overcurrent Protection

N/A 15 A

Power Supply Conduit Hole Diameter

N/A 1.125 in

Low-Voltage Conduit Hole Diameter

N/A 0.5 in

Depth

N/A 74 in

Width

N/A 48-5/16 in

Height

N/A 39-7/8 in

N/A Installation
Daikin Packaged units are designed with fast and easy installation in mind and are ideal for both new construction and retrofit projects. Our packaged rooftop units are built to be a direct replacement for most rooftop units in the field without the need of a curb adapter, to be able to replace the unit in a shorter time and at a lower cost.

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors to match the required total load.

Supply Fan
The direct-drive airfoil single width, single inlet (SWSI) Class II construction supply fan with aluminum fan blades provides efficient and quiet operation at wide ranging static pressure and air flow requirements.

Coils
All units use large face area outdoor coils. These coils are constructed with seamless copper tubes, mechanically bonded into aluminum plate-type fins with full drawn collars to completely cover the tubes for high operating efficiencies.

Heat Pump Heating
Evaporator coil, condenser coil, compressors and refrigerant circuit are designed for heat pump operation.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use weatherproof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and long lasting component maintenance.

Heating Section
Wide ranging of electric heat selections effectively handle most comfort heating demand from morning warm-up control to full heat.

Electric Heat
ETL approved electric heat is factory assembled, installed and tested.

Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.