Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
- Capacity range from 3 to 6 tons
- Numerous voltages and phases for application flexibility
- All units has a choice of 3-phase 208/230V, 460V or 575V
- 3-5 ton units also have a choice of 1-phase 208/230V
- All models have ECM Direct-Drive Indoor Fan Motor
- Designed to fit standard curb sizes for ease of many replacements
Unit of Measure
Cooling Capacity |
N/A 36000 Btu/h3 TR |
SEER |
N/A 17 |
EER |
N/A 12.6 |
Heating Capacity |
N/A 36000 Btu/h |
HSPF |
N/A 8.2 |
Sound Level |
N/A 75 dB |
Operating Weight |
N/A 595 lb |
Shipping Weight |
N/A 653 lb |
Motor Type |
N/A Direct Drive |
External Static Pressure (ESP) |
N/A Standard |
Wheel Dia. x Width |
N/A 12 x 11 in |
Indoor Nominal CFM |
N/A 1200 |
Evaporator Motor - RPM |
N/A 1200 |
Evaporator Motor Horsepower |
N/A 3/4 hp |
Filter Size |
N/A 14 x 20 x 2 (4) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 216 oz |
Evaporator Coil Face Area |
N/A 7.3 ft² |
Rows Deep |
N/A 4 |
Fins per Inch |
N/A 16 |
Outdoor Horsepower |
N/A 1 |
RPM (High/Low stage) |
N/A 810 |
Outdoor Horsepower |
N/A 0.17 hp |
Diameter |
N/A 22 in |
No. of Fan Blades |
N/A 3 |
Condenser Coil Face Area |
N/A 19.31 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 16 |
Quantity |
N/A 1 |
Type |
N/A Scroll |
Stage |
N/A 2 |
Rated Load Amps |
N/A 11.6 A |
Locked Rotor Amps |
N/A 73 A |
Voltage |
N/A 208-230 V |
Number of Phases |
N/A 3 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 5.7 A |
Max External Static |
N/A 0.75 inWc |
Outdoor Fan FLA |
N/A 0.95 A |
Min. Circuit Ampacity |
N/A 21.2/21.2 A |
Max. Overcurrent Protection |
N/A 25/25 A |
Power Supply Conduit Hole Diameter |
N/A 1.125 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.5 in |
Depth |
N/A 74 in |
Width |
N/A 48-5/16 in |
Height |
N/A 43 1/2 in |