Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
Unit of Measure

Type

N/A Air-Cooled Split Indoor Unit

Color

N/A White

Voltage

N/A 208 to 230 V

Frequency

N/A 60 Hz

Number of Phases

N/A 1

Rated Cooling Capacity

N/A 22400 Btu/h6.57 kW

Rated Cooling Capacity (Min. - Max.)

N/A 7000 to 26400 Btu/h2.05 to 7.74 kW

Rated Heating Capacity

N/A 23600 Btu/h6.92 kW

Rated Heating Capacity (Min. - Max.)

N/A 6200 to 28600 Btu/h1.82 to 8.38 kW

Moisture Removal

N/A 0.88 gal/h

Rated Running Current - Cooling

N/A 8.12 A

Rated Running Current - Heating

N/A 9.0 A

Rated Power Consumption - Cooling

N/A 1867 W

Rated Power Consumption - Heating

N/A 2070 W

Refrigerant Type

N/A R32

Refrigerant Charge

N/A 3.31 lb1.50 kg

Amount of Additional Charge of Refrigerant

N/A 0.18 oz/ft17 g/m

Airflow Rate (Turbo)

N/A 754 ft³/min

Airflow Rate (High)

N/A 716 ft³/min

Airflow Rate (Medium)

N/A 605 ft³/min

Airflow Rate (Low)

N/A 467 ft³/min

Airflow Rate (Quiet)

N/A 395 ft³/min

Sound Pressure Level (H/M/L/Q) - Cooling

N/A 53/45/39/34 dBA

Sound Pressure Level (H/M/L/Q) - Heating

N/A 53/43/38/34 dBA

Fan Type

N/A Cross Flow

Fan Drive

N/A Direct

Fan Speed

N/A 3 Steps, Auto, Quiet, Turbo

Fan Motor Type

N/A Direct Current

Fan Motor Output

N/A 39 W

Fan Motor Running Current (Rated)

N/A 0.17 A

Fan Motor Power Consumption (Rated)

N/A 54 W

Air Direction Control

N/A Up, Down, Left, Right

Air Filter

N/A Catechin

Rated Cooling Conditions

N/A Indoor: 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB) Outdoor: 95°FDB (35°CDB)

Rated Heating Conditions

N/A Indoor: 70°FDB (21.1°CDB) Outdoor: 47°FDB (8.3°CDB) / 43°FWB(6.1°CWB)

Weight

N/A 30.5 lb13.8 kg

Gross Weight

N/A 36 lb16.5 kg

EER2

N/A 12.0

SEER2

N/A 21.0

COP

N/A 3.34

HSPF2

N/A 9.10

Min. Circuit Ampacity

N/A 16.34 A

Max. Fuse Ampacity

N/A 20 A

Depth

N/A 10-3/4 in273 mm

Width

N/A 39-9/16 in990 mm

Height

N/A 11-11/16 in297 mm

Packaged Depth

N/A 14 5/8 in371 mm

Packaged Width

N/A 42-1/4 in1073 mm

Packaged Height

N/A 14 3/4 in375 mm

Pipe Connections - Liquid

N/A 1/4 in6.35 mm

Pipe Connections - Gas

N/A 5/8 in15.88 mm

Condensate Drain Size

N/A 5/8 in16 mm

Max. Interunit Height Difference

N/A 65-5/8 ft20 m

Max. Interunit Piping Length

N/A 98-1/2 ft30 m

Chargeless

N/A 32-13/16 ft10 m

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.