Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
-
Packed with advanced technology, VRV IV X is the industry's first 3-phase variable refrigerant flow system with dual-fuel capability. The new series is equipped with features to optimize initial capital required on phased installations and provides ease of service and maintenance.
- VRV with Variable Refrigerant Temperature (VRT) technology
- Industry’s first 3-phase variable refrigerant flow system to integrate with communicating gas furnaces
- Design flexibility to enlarge system from single to dual module or dual to triple module without change to installed main pipe sizes – refer to the VRV IV X engineering manual for details
- Capacity range from 6 to 38 tons
- 208-230V / 3ph / 60Hz (REYQ_XBTJA)
- 460V / 3ph / 60Hz (REYQ_XBYDA)
- 575V / 3ph / 60Hz (REYQ_TBYCA)
Unit of Measure
Unit Combination |
N/A 2 x REYQ144XBYDA REYQ120XBYDA |
Nominal Cooling Capacity |
N/A 406000 Btu/h119.6 kW |
Rated Cooling Capacity |
N/A 388000 Btu/h113.7 kW |
Nominal Heating Capacity |
N/A 459000 Btu/h134.5 kW |
Rated Heating Capacity |
N/A 394000 Btu/h115.5 kW |
Power Supply |
N/A 3 phase, 460 V, 60 Hz |
Min/Max Volts |
N/A 416/508 V |
Maximum Overcurrent Protection |
N/A 25 + 40 + 40 A |
Min. Circuit Ampacity |
N/A 21.1 + 27.9 + 27.9 A |
Compressor Rated Load Amps |
N/A 16.2 + 20.4 + 20.4 A |
Outdoor Fan Motor - Rated Output |
N/A (0.6 × 2) × 3 kW(1.0 × 2) × 3 A |
Short-Circuit Current Rating |
N/A SCCR kA rms, Symmetrical 600 V MAX: 5 |
Color |
N/A Ivory White (5Y7.5/1) |
Heat Exchanger |
N/A Cross Fin Coil |
Compressor Type |
N/A Hermetically sealed scroll type |
Compressor Volume |
N/A 20.9 + 23.7 + 23.7 m³/h |
Compressor Number of Revolutions |
N/A 6.162 + 4.470 + 4.470 rpm |
Compressor Motor Output x Number of Units |
N/A 6.4 x 1 + 6.8 x 1 + 6.8 x 1 kW |
Compressor Starting Method |
N/A Soft Start |
Fan Type |
N/A Propeller fan |
Fan Motor Output |
N/A (0.6 x 2) x 3 kW |
Fan Air Flow Rate |
N/A 7989 + 9480 + 9480 ft³/min226 + 268 + 268 m³/min |
Fan Drive |
N/A Direct drive |
Weight |
N/A 330 + 330 + 360 kg727 + 727 + 793 lb |
Sound Level |
N/A 70.5 dB |
Sound Power Level (Reference Data) |
N/A 90.5 dB |
Safety Devices |
N/A High Pressure Switch, Fan Driver Overload Protector, Overcurrent Fuse, Inverter Overload Protector, Leak Detecting Device |
Defrost Method |
N/A Deicer |
Capacity Control |
N/A 3.0 to 100 % |
Refrigerant Name |
N/A R410A |
Refrigerant Control |
N/A Electronic Expansion Valve |
Refrigerant Charge |
N/A 25.8 + 25.8 + 25.8 lb11.7 + 11.7 + 11.7 kg |
Standard Accessories |
N/A Installation Manual, Operation Manual, Connection Pipes, Clamps |
Height |
N/A 66-11/16 + 66-11/16 + 66-11/16 in1694 + 1694 + 1694 mm |
Width |
N/A 48-7/8 + 48-7/8 + 48-7/8 in1242 + 1242 + 1242 mm |
Depth |
N/A 30-3/16 + 30-3/16 + 30-3/16 in767 + 767 + 767 mm |
Pipe Connections - Liquid |
N/A 3/4 in19.1 mm |
Pipe Connections - Suction Gas Pipe |
N/A 1-5/8 in41.3 mm |
Pipe Connections - High/Low Pressure Gas |
N/A 1-3/8 in34.9 mm |
System Performance Heating COP 17F Ducted |
N/A 2.05 |
System Performance Heating COP 17F Non-Ducted |
N/A 2.05 |
System Performance Heating COP 47F Ducted |
N/A 3.2 |
System Performance Heating COP 47F Non-Ducted |
N/A 3.28 |
System Performance EER Ducted |
N/A 9.2 |
System Performance EER Non-Ducted |
N/A 9.1 |
System Performance IEER Ducted |
N/A 16 |
System Performance IEER Non-Ducted |
N/A 16.2 |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.