Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
-
Packed with advanced technology, VRV IV X is the industry's first 3-phase variable refrigerant flow system with dual-fuel capability. The new series is equipped with features to optimize initial capital required on phased installations and provides ease of service and maintenance.
- VRV with Variable Refrigerant Temperature (VRT) technology
- Industry’s first 3-phase variable refrigerant flow system to integrate with communicating gas furnaces
- Design flexibility to enlarge system from single to dual module or dual to triple module without change to installed main pipe sizes – refer to the VRV IV X engineering manual for details
- Capacity range from 6 to 38 tons
- 208-230V / 3ph / 60Hz (REYQ_XBTJA)
- 460V / 3ph / 60Hz (REYQ_XBYDA)
- 575V / 3ph / 60Hz (REYQ_TBYCA)
Unit of Measure
Nominal Cooling Capacity |
N/A 96000 Btu/h28.1 kW |
Rated Cooling Capacity |
N/A 92000 Btu/h27.0 kW |
Nominal Heating Capacity |
N/A 108000 Btu/h31.7 kW |
Rated Heating Capacity |
N/A 103000 Btu/h30.2 kW |
Power Supply |
N/A 3 phase, 460 V, 60 Hz |
Min/Max Volts |
N/A 416/508 V |
Maximum Overcurrent Protection |
N/A 25 A |
Min. Circuit Ampacity |
N/A 21.1 A |
Compressor Rated Load Amps |
N/A 10.5 A |
Outdoor Fan Motor - Rated Output |
N/A 0.6 × 2 kW1.0 × 2 A |
Short-Circuit Current Rating |
N/A SCCR kA rms, Symmetrical 600 V MAX: 5 |
Color |
N/A Ivory White (5Y7.5/1) |
Heat Exchanger |
N/A Cross Fin Coil |
Compressor Type |
N/A Hermetically sealed scroll type |
Compressor Volume |
N/A 17.4 m³/h |
Compressor Number of Revolutions |
N/A 5.142 rpm |
Compressor Motor Output x Number of Units |
N/A 5.4 x 1 kW |
Compressor Starting Method |
N/A Soft Start |
Fan Type |
N/A Propeller fan |
Fan Motor Output |
N/A 0.6 x 2 kW |
Fan Air Flow Rate |
N/A 7989 ft³/min226 m³/min |
Fan Drive |
N/A Direct drive |
Weight |
N/A 330 kg727 lb |
Sound Level |
N/A 65 dB |
Sound Power Level (Reference Data) |
N/A 80 dB |
Safety Devices |
N/A High Pressure Switch, Fan Driver Overload Protector, Overcurrent Fuse, Inverter Overload Protector, Leak Detecting Device |
Defrost Method |
N/A Deicer |
Capacity Control |
N/A 13 to 100 % |
Refrigerant Name |
N/A R410A |
Refrigerant Control |
N/A Electronic Expansion Valve |
Refrigerant Charge |
N/A 25.8 lb11.7 kg |
Standard Accessories |
N/A Installation Manual, Operation Manual, Connection Pipes, Clamps |
Height |
N/A 66-11/16 in1694 mm |
Width |
N/A 48-7/8 in1242 mm |
Depth |
N/A 30-3/16 in767 mm |
Pipe Connections - Liquid |
N/A 3/8 in9.5 mm |
Pipe Connections - Suction Gas Pipe |
N/A 7/8 in22.2 mm |
Pipe Connections - High/Low Pressure Gas |
N/A 3/4 in19.1 mm |
System Performance Heating COP 17F Ducted |
N/A 2.26 |
System Performance Heating COP 17F Non-Ducted |
N/A 2.32 |
System Performance Heating COP 47F Ducted |
N/A 3.5 |
System Performance Heating COP 47F Non-Ducted |
N/A 3.75 |
System Performance EER Ducted |
N/A 11.6 |
System Performance EER Non-Ducted |
N/A 11.4 |
System Performance IEER Ducted |
N/A 18.3 |
System Performance IEER Non-Ducted |
N/A 20.4 |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.