Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
Daikin VRV EMERION is available in single and dual-module lineups. The introduction of new 16-20 T single modules allows a system capacity of up to 40 Tons with just two modules. This helps reduce the overall space required for mechanical equipment and optimizes total project costs.
- VRV with Variable Refrigerant Temperature (VRT) technology
- High energy efficiency with IEERs up to 30.0
- Capacity range from 6 to 40 tons
- 208-230V / 3ph / 60Hz (REYQ_XATJB)
- 460V / 3ph / 60Hz (REYQ_XAYDB)
Unit of Measure
Nominal Cooling Capacity |
N/A 430000 Btu/h127 kW |
Rated Cooling Capacity |
N/A 410000 Btu/h120 kW |
Nominal Heating Capacity |
N/A 486000 Btu/h142 kW |
Rated Heating Capacity |
N/A 404000 Btu/h118 kW |
Power Supply |
N/A 3 phase, 60 Hz, 208/230 V |
Casing Color |
N/A Ivory White (5Y 7.5/1) |
Heat Exchanger |
N/A Cross Fin Coil |
Sound Pressure Level (Reference Date) |
N/A 72 dB |
Sound Power Level (Reference Data) |
N/A 95 dB |
Unit Combination |
N/A REYQ216AATJB |
Safety Devices |
N/A High Pressure Switch, Fan Driver Overload Protector, Overcurrent Fuse, Inverter Overload Protector, Leak Detecting Device |
Defrost Method |
N/A Deicer |
Capacity Control |
N/A 1 to 100 % |
Standard Accessories |
N/A Installation Manual, Operation Manual, Connection Pipes, Clamps |
Weight |
N/A 957 + 957 lb434 + 434 kg |
Min/Max Volts |
N/A 187/253 V |
Min. Circuit Ampacity |
N/A 67.2 + 67.2 A |
Maximum Overcurrent Protection |
N/A 80 + 80 A |
Rated Load Amps |
N/A (28.0 + 28.1) + (28.0 + 28.1) A |
Outdoor Fan Motor - Rated Output |
N/A (0.95 x 2) x 2 kW(3.4 x 2) x 2 A |
Short-Circuit Current Rating |
N/A SCCR kA rms, Symmetrical 600 V MAX: 5 |
Type |
N/A Hermetically sealed scroll type |
Volume |
N/A (16.7 + 16.7) + (16.7 + 16.7) m³/h |
Number of Revolutions |
N/A (5232 + 5232) + (5232 + 5232) rpm |
Motor Output x Number of Units |
N/A (6.56 + 6.56) + (6.56 + 6.56) kW |
Starting Method |
N/A Soft Start |
Type |
N/A Propeller fan |
Motor Output |
N/A 0.95 x 2 + 0.95 x 2 kW |
Air Flow Rate |
N/A 14505 + 14505 ft³/min410.8 + 410.8 m³/min |
Fan Drive |
N/A Direct drive |
Refrigerant Name |
N/A R410A |
Refrigerant Charge |
N/A 25.8 + 25.8 lb11.7 + 11.7 kg |
Refrigerant Control |
N/A Electronic Expansion Valve |
Dimensions: (H x W x D) |
N/A 65-3/8 x 68-7/8 x 30-1/8 + 65-3/8 x 68-7/8 x 30-1/8 in1660 x 1750 x 765 + 1660 x 1750 x 765 mm |
Pipe Connections - Liquid |
N/A 3/4 in19.1 mm |
Pipe Connections - Suction Gas Pipe |
N/A 1-5/8 in41.3 mm |
Pipe Connections - High/Low Pressure Gas |
N/A 1-3/8 in34.9 mm |
System Performance Heating COP 17F Ducted |
N/A 2.05 |
System Performance Heating COP 17F Non-Ducted |
N/A 2.05 |
System Performance Heating COP Ducted |
N/A 3.2 |
System Performance Heating COP Non-Ducted |
N/A 3.3 |
System Performance EER Ducted |
N/A 9.2 |
System Performance EER Non-Ducted |
N/A 9.8 |
System Performance IEER Ducted |
N/A 16.3 |
System Performance IEER Non-Ducted |
N/A 18.1 |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.