  • Variable Refrigerant Temperature (VRT) technology allows VRV IV-S series to deliver improved efficiencies and year round comfort
  • 3, 4, and 5 ton capacities available
  • 208-230V / 1Ph / 60 Hz
Unit of Measure

Model Type

N/A Heat Pump Unit

Heat Exchanger Type

N/A Cross Fin Coil

Color

N/A Ivory White

Voltage

N/A 208/230 V

Phase

N/A 1

Frequency

N/A 60 Hz

Cooling Capacity

N/A 57500 Btu/h16.7 kW

Nominal Heating Capacity

N/A 57000 Btu/h16.7 kW

Rated Heating Capacity (at 17°F) - Ducted

N/A 36400 Btu/h

Rated Heating Capacity (at 17°F) - Non-Ducted

N/A 37000 Btu/h

Rated Heating Capacity (at 17°F) - Mixed

N/A 36700 Btu/h

Rated Heating Capacity (at 47°F) - Ducted

N/A 57000 Btu/h

Rated Heating Capacity (at 47°F) - Non-Ducted

N/A 57000 Btu/h

Rated Heating Capacity (at 47°F) - Mixed

N/A 57000 Btu/h

Standard Compliance

N/A UL

Compressor Type

N/A Hermetically Sealed Swing Type

Airflow Rate

N/A 3741 ft³/min

Safety Devices

N/A High Pressure Switch, Fan Driver Overload Protector, Inverter Overload Protector, Fusible Plug, Fuse

Weight

N/A 102 kg225 lb

System Performance EER2 Ducted

N/A 8.5

System Performance EER Ducted

N/A 8.5

System Performance EER2 Non-Ducted

N/A 9.8

System Performance EER Non-Ducted

N/A 9.8

System Performance EER Mixed

N/A 9.2

System Performance SEER2 Ducted

N/A 15.5

System Performance SEER Ducted

N/A 15.5

System Performance SEER2 Non-Ducted

N/A 20.5

System Performance SEER Non-Ducted

N/A 18.6

System Performance SEER Mixed

N/A 17.1

System Performance HSPF2 Ducted

N/A 8.5

System Performance HSPF Ducted

N/A 8.5

System Performance HSPF2 Non-Ducted

N/A 9.5

System Performance HSPF Non-Ducted

N/A 8.5

System Performance HSPF Mixed

N/A 8.5

COP (at 17°F) - Ducted

N/A 2.7

COP (at 17°F) - Non-Ducted

N/A 3.2

COP (at 17°F) - Mixed

N/A 3.0

COP (at 47°F) - Ducted

N/A 3.70

COP (at 47°F) - Non-Ducted

N/A 4.3

COP (at 47°F) - Mixed

N/A 4.00

Height

N/A 52-15/16 in1345 mm

Width

N/A 35-7/16 in900 mm

Depth

N/A 12 5/8 in320 mm

Pipe Connections - Liquid

N/A 3/8 in9.5 mm

Pipe Connections - Gas

N/A 3/4 in19.1 mm

Clearance Front Depth

N/A 20 in

Clearance Top Depth

N/A 40 in

Liquid Pipe Horizontal Offset

N/A 1.4375 in

Liquid Pipe Vertical Offset

N/A 4.4375 in

Gas Pipe Height

N/A 17.9375 in

Liquid Pipe Height

N/A 18.6875 in

Gas Pipe Horizontal Offset

N/A 2.5625 in

Gas Pipe Vertical Offset

N/A 1.4375 in

Pipe Length

N/A 0.5 in

Maximum allowable length between OD and ID unit - Actual Piping Length

N/A 394 ft120 m

Maximum allowable length between OD and ID unit -Equivalent Piping Length

N/A 492 ft150 m

Maximum allowable length between OD and ID unit - Total Piping Length

N/A 984 ft300 m

Maximum allowable length after branch - Actual Piping Length

N/A 131 ft40 m

Maximum allowable height difference between OD and ID units - Difference in Height

N/A 165 ft50 m

Maximum allowable height difference between ID and ID units - Difference in Height

N/A 49 ft15 m

Heating Capacity Note

N/A Indoor temp.: 70 ºFDB (21.1 ºCDB) / outdoor temp.: 47 ºFDB (8.3 ºCDB), 43 ºFWB (6.1 ºCWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0.

Cooling Capacity Note

N/A Indoor temp.: 80 ºFDB (26.7 ºCDB), 67 ºFWB (19.4 ºCWB) / outdoor temp.: 95 ºFDB (35.0 ºCDB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0.