Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
Can be applied to both geothermal and boiler/tower applications as standard
- Small condensers can be triple stacked for reduced installation space and increased usable square footage
- VRV with Variable Refrigerant Temperature (VRT)
- Refrigerant cooled inverter technology to deliver consistent and reliable PCB operations
- Drop-down electrical box for easy service to key components
- Field selectable top or front refrigerant connections for flexible and easy installation
- 575V / 3ph / 60Hz (RWEQ_TBYCU)
Model Type |
N/A Heat Recovery |
Heat Exchanger Type |
N/A Stainless Steel Plate |
Color |
N/A Ivory White (5Y7.5/1) |
Cooling Capacity |
N/A 126.6 kW402000 Btu/h |
Heating Capacity |
N/A 486000 Btu/h142.4 kW |
Power Supply |
N/A 575 V, 60 Hz, 3 phase |
Voltage |
N/A 575 V |
Phase |
N/A 3 |
Frequency |
N/A 60 Hz |
Compressor Type |
N/A Hermetically Sealed Scroll |
Compressor Displacement |
N/A 28.5 + 28.5 + 28.5 m³/h1,006 + 1,006 + 1,006 ft³/h |
Safety Devices |
N/A High Pressure Switch, Inverter Overload Protector, Fusible Plug, Leak Detecting Device, Overcurrent Fuse |
Weight |
N/A 200 + 200 + 200 kg440.9 + 440.9 + 440.9 lb |
Height |
N/A (38-9/16) x 3 in(980) x 3 mm |
Width |
N/A (30-1/8) x 3 in(765) x 3 mm |
Depth |
N/A (22-1/16) x 3 in(560) x 3 mm |
Pipe Connections - Gas |
N/A 1-5/8 (41.3) C1220T (Brazing Connection) -Main Line- |
Pipe Connections - Water Inlet |
N/A ISO 228-1-G1 1/4B (External thread) |
Pipe Connections - Water Outlet |
N/A ISO 228-1-G1 1/4B (External thread) |
System Performance IEER Ducted |
N/A 14.8 |
System Performance IEER Non-Ducted |
N/A 16.2 |
System Performance COP Ducted |
N/A 4.01 |
System Performance Heating COP Non-Ducted |
N/A 4.2 |
System Performance SCHE Ducted |
N/A 15.1 |
System Performance SCHE Non-Ducted |
N/A 14.4 |
N/A
|
N/A
|
Cooling Capacity Note |
N/A Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB)/Inlet water temp.: 86°F (30°C). Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m). |
Heating Capacity Note |
N/A Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB)/Inlet water temp.: 68°F (20°C). Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m). |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.