Print Back
20 Ton AC Direct Drive 3 Phase 208-230V
Unit of Measure

Specifications

Type

N/A Light Commercial Packaged Air Conditioner

Cooling Capacity

N/A 230000 Btu/h20 T

IEER

N/A 11.0

System Performance EER

N/A 14.2

AHRI Reference #

N/A 210331719

Sound Level

N/A 92.1 dB

Operating Weight

N/A 1993 lb

Shipping Weight

N/A 2108 lb

Evaporator Motor / Coil

Evaporator Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 15 x 15 in

Indoor Nominal CFM

N/A 6500

RPM

N/A 300-1600

Evaporator Motor Horsepower

N/A 3.5 hp

Filter Size

N/A 20 x 20 x 2 (8) in

Drain Size (NPT)

N/A 1 in

R-410A Refrigerant Charge

N/A 186/165 oz

Evaporator Coil Face Area

N/A 21.69 ft²

Rows Deep

N/A 4

Fins per Inch

N/A 18

Condenser Fan / Coil

Quantity of Condenser Fan Motors

N/A 4

RPM (High/Low stage)

N/A 1130

Outdoor Horsepower

N/A 1/2 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 25.7 ft²

Rows Deep

N/A 1

Fins per Inch

N/A 23

Compressor

Quantity

N/A 2

Type

N/A Scroll

Rated Load Amps

N/A 28.2 A

Locked Rotor Amps

N/A 240 A

Electrical Data

Voltage

N/A 208 to 230 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 10.9 A

Max External Static

N/A 1.2 inWc

Outdoor Fan FLA

N/A 2.7 A

Min. Circuit Ampacity

N/A 96.1 / 96.1 A

Max. Overcurrent Protection

N/A 110 / 110 A

Power Supply Conduit Hole Diameter

N/A 2.5 in

Low-Voltage Conduit Hole Diameter

N/A 0.5 in

Dimensions

Depth

N/A 133 7/8 in

Width

N/A 88 1/2 in

Height

N/A 51 in

Features and Benefits

N/A Installation
Daikin Packaged units are designed with fast and easy installation in mind and are ideal for both new construction and retrofit projects.

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors with stage control to match the required total load for efficient part load control.

Supply Fan
Supply fan will be 2 direct-drive motors. Ball bearing DirectDrive EEM motor removes the need for belts, sheaves, bearings and lubrication.

Coils
The indoor coil section is installed in a draw through configuration to provide better dehumidification. These coils are constructed with seamless copper tubes, mechanically bonded into aluminum plate-type fins with full drawn collars to completely cover the tubes for high operating efficiencies.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use, weatherproof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and long lasting component maintenance.

Heating Section
Wide range of electric heat selections effectively handle most comfort heating demand from morning warm-up control to full heat.

Electric Heat
ETL approved electric heat is factory assembled, installed and tested.

Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.