Print Back
Base efficiency Air Conditioner rooftop unit available with field and factory installed accessories for easy installation and serviciability.
Unit of Measure

Specifications

Model Type

Air Conditioner Units

Cooling Capacity

114000 Btu/h10 T

System Performance EER

11.2

System Performance IEER

12.9

Sound Level

82 dBA

Operating Weight

1070 lb

Shipping Weight

1150 lb

Evaporator Motor / Coil

Motor Type

Belt Drive

External Static Pressure (ESP)

Standard

Wheel Dia. x Width

15 X 15 in

Indoor Nominal CFM

3600

Evaporator Motor - RPM

1740

Evaporator Motor Horsepower

2.00 hp

Filter Size

20 X 20 X 2 (4) in

Drain Size (NPT)

3/4 in

R410A Refrigerant Charge

103.5/103 oz

Evaporator Coil - Face Area

11 ft²

Evaporator Coil - Rows Deep

4

Evaporator Coil - Fins per Inch

16

Condenser Fan / Coil

Quantity of Condenser Fan Motors

2

RPM (High/Low stage)

1050

Outdoor Horsepower

0.33 hp

Diameter

22 in

No. of Fan Blades

3

Condenser Coil Face Area

31.3 ft²

Rows Deep

2

Fins per Inch

28

Compressor

Quantity

2

Type

Scroll

Stage

1

Rated Load Amps

7.8 A

Locked Rotor Amps

52.0 A

Electrical Data

Voltage

460 V

Phase

3

Frequency

60 Hz

Indoor Blower FLA

2.9 A

Max External Static

0.8 inWc

Outdoor Fan FLA

0.85 A

Min. Circuit Ampacity

22.1 A

Max. Overcurrent Protection

25 A

Power Supply Conduit Hole Diameter

1.375 in

Low-Voltage Conduit Hole Diameter

0.375 in

Dimensions

Depth

93-3/4 in

Width

60-3/8 in

Height

54.25 in

Features

N/A

  • Capacity Range from 7.5 to 12.5 tons
  • Belt Drive flexibility
  • Two stage capacity for partial load