  • Heavy-duty stainless-steel heat exchanger
  • High-efficiency two-stage scroll compressor with factory-installed sound blanket
  • Multi-speed ECM indoor blower motor
  • All-aluminum evaporator coil
  • TXV expansion device
  • Single-stage gas valve
  • Power-assisted combustion
  • All blower operation and all safety circuits complete with self-diagnostics
  • Loss-of-charge protection and high-pressure switch
  • Direct-spark ignition system with microprocessor-based control for the entire ignition sequence
  • Eligible for installation in California’s South Coast Air Quality Management District (SCAQMD) and San Joaquin Valley Air Pollution Control District (SJVUAPCD). For California’s South Coast Air Quality Management District (SCAQMD) only: This furnace complies with the SCAQMD Rule 1111 14ng/j NOx emission limit.
  • AHRI Cerified
  • ETL Listed
Unit of Measure

Specifications

Cooling Capacity

N/A 29000 Btu/h2 1/2 T

Sensible Cooling Capacity

N/A 22500 Btu/h

Seasonal Energy Efficiency Rating SEER2

N/A 14.6

EER2

N/A 11.2

Decibels

N/A 76 dB

AHRI Reference #s

N/A 209319560

Refrigerant Type

N/A R-410A

Weight

N/A 407 lb

Shipping Weight

N/A 407 lb

Heating Capacity

Heating Capacity - Input

N/A 80000 Btu/h

Heating Capacity - Output

N/A 64000 Btu/h

AFUE

N/A 81 %

Temperature Rise Range

N/A 35 to 65 ºF

No. of Burners

N/A 1

Evaporator Motor

Type

N/A ECM

Wheel (D x W)

N/A 10 x 9 in

Motor Indoor Nominal CFM

N/A 700 L ft³/min950 H ft³/min

No. Of Speed

N/A Variable

Horsepower

N/A 1/2 hp

Evaporator Coil

Face Area

N/A 4.3 ft²

Rows Deep

N/A 3

Fins per Inch

N/A 14

Piston Size (Cooling)

N/A TXV

Drain Size (NPT)

N/A 3/4 in3/4

Refrigerant Charge

N/A 64 oz

Condenser Fan / Coil

Horsepower

N/A 1/4 hp

RPM

N/A 830

Fan Diameter

N/A 22 in

Fan Blades

N/A 3

Outdoor Nominal CFM

N/A 2200 ft³/min

Face Area

N/A 8.7 ft²

Rows Deep

N/A 2

Fins per Inch

N/A 27

Compressor

Quantity

N/A 1

Type

N/A 2-Stg Scroll

Stage

N/A Two

Rated Load Amps

N/A 13.1 A

Locked Rotor Amps

N/A 73.0 A

Electrical Data

Voltage

N/A 208 to 230 V

Number of Phases

N/A 1

Frequency

N/A 60 Hz

Indoor Blower - Full Load Amps

N/A 4.3 A

Outdoor Fan - Full Load Amps

N/A 1.3 A

Outdoor Fan - Locked Rotor Amps

N/A 3.0 A

Min. Circuit Ampacity

N/A 22.0 A

Max. Overcurrent Protection

N/A 35 A

Dimensions

Depth

N/A 51 in

Width

N/A 47 in

Height

N/A 34 1/2 in

Features

N/A Standard Features

  • Heavy-duty stainless-steel heat exchanger
  • High-efficiency two-stage scroll compressor with factory-installed sound blanket
  • Variable-speed ECM indoor blower motor
  • All-aluminum evaporator coil
  • TXV expansion device
  • Single-stage gas valve
  • Power-assisted combustion
  • All blower operation and all safety circuits complete with self-diagnostics
  • Loss-of-charge protection and high-pressure switch
  • Direct-spark ignition system with microprocessor-based control for the entire ignition sequence
  • Eligible for installation in California’s South Coast Air Quality Management District (SCAQMD) and San Joaquin Valley Air Pollution Control District (SJVUAPCD). For California’s South Coast Air Quality Management District (SCAQMD) only: This furnace complies with the SCAQMD Rule 1111 14ng/j NOx emission limit.
  • AHRI Cerified
  • ETL Listed
Cabinet Features
  • Fully insulated heavy-gauge, zinc-coated steel cabinet with UV-resistant grey powder-paint finish
  • Aluminum foil-facing internal insulation reinforced with fiberglass scrim
  • Louvered condenser coil protection
  • Compressor sound blanket
  • Compressor grommets for vibration isolation
  • Horizontal or downflow application
  • Convenient access panels
  • Bottom 2" high base rails for easier handling
  • When properly anchored, meets the 2020 Florida Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)