Print Back
10 Ton Heat Pump Direct Drive 3 Phase 208-230V
Unit of Measure

Specifications

Type

N/A Light Commercial Packaged Heat Pump

Cooling Capacity

N/A 116000 Btu/h10 T

IEER

N/A 14.1

System Performance EER

N/A 11

AHRI Reference #

N/A 210446543

Sound Level

N/A 86.8 dB

Operating Weight

N/A 1154 lb

Shipping Weight

N/A 1234 lb

Heating Capacity

Heating Capacity

N/A 116000 Btu/h

Evaporator Motor / Coil

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 15 x 15 in

Indoor Nominal CFM

N/A 3850

RPM

N/A 300-1600

Evaporator Motor Horsepower

N/A 3.5 hp

Filter Size

N/A 20 x 25 x 2 (2) in25 x 25 x 2 (2) in

Drain Size (NPT)

N/A 3/4 in

R-410A Refrigerant Charge

N/A 154/154 oz

Evaporator Coil Face Area

N/A 15 ft²

Rows Deep

N/A 3

Fins per Inch

N/A 16

Condenser Fan / Coil

Quantity of Condenser Fan Motors

N/A 2

RPM (High/Low stage)

N/A 1130

Outdoor Horsepower

N/A 1/2 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 33.3 ft²

Rows Deep

N/A 2

Fins per Inch

N/A 16

Compressor

Quantity

N/A Scroll

Type

N/A 2

Stage

N/A 1

Rated Load Amps

N/A 15.6 A

Locked Rotor Amps

N/A 110.0 A

Electrical Data

Voltage

N/A 208 to 230 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 10.9 A

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 2.7 A

Min. Circuit Ampacity

N/A 51.5/51.5 A

Max. Overcurrent Protection

N/A 60/60 A

Power Supply Conduit Hole Diameter

N/A 1.375 in

Low-Voltage Conduit Hole Diameter

N/A 0.5 in

Dimensions

Depth

N/A 93-3/4 in

Width

N/A 60-3/8 in

Height

N/A 54-5/8 in

Features and Benefits

N/A Installation
Daikin Packaged units are designed with fast and easy installation in mind and are ideal for both new construction and retrofit projects. Our packaged rooftop units are built to be a direct replacement for most rooftop units on the field without the need of a curb adapter, to be able to replace the unit in a shorter time and at a lower cost.

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors to match the required total load.

Supply Fan
The direct-drive with airfoil single width, single inlet (SWSI) Class II construction supply fan with aluminum fan + blades provides efficient and quiet operation at wide ranging static pressure and air flow requirments.

Coils
The indoor coil section is installed in a draw through configuration to provide better dehumidification.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use weatherproof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and long lasting component maintenance.

Heating Section
Wide ranging of electric heat selections effectively handle most comfort heating demand from morning warm-up control to full heat.

Electric Heat
ETL approved electric heat is factory assembled, installed and tested.

Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.