Print Back
Unit of Measure

Specifications

Model Type

N/A Round Flow Ceiling Cassette

Cooling Capacity

N/A 18000 Btu/h

Heating Capacity

N/A 20000 Btu/h

Optional Outside Air Intake Kit

N/A No

Fan Air Flow Rate

N/A 560 ft³/min

Cooling Power Input

N/A 56 W

Heating Power Input

N/A 42 W

Sound Pressure Level

N/A 32 dBA

Outside Air Intake Kit

N/A No

Power Supply

N/A 208/230 VAC, 60 Hz, 1 phase

Minimum Circuit Ampacity

N/A 0.4 A

Maximum Overcurrent Protection

N/A 15 A

Weight

N/A 19.5 kg43 lb

Dimensions

Depth

N/A 33-1/16 in840 mm

Width

N/A 33-1/16 in840 mm

Height

N/A 9-11/16 in246 mm

Pipe Connections - Liquid

N/A 1/4 in6.4 mm

Pipe Connections - Gas

N/A 1/2 in12.7 mm

Pipe Connections - Drain - External Diameter

N/A 1 1/4 in31.8 mm

Pipe Connections - Drain - Internal Diameter

N/A 1 in25.4 mm

System Efficiency Metrics

System Performance SEER

N/A 17.2

System Performance EER

N/A 13.9 Btu/h-W

System Performance HSPF

N/A 10.1

Features

N/A

  • 23 configurable airflow patterns ensure ideal air distribution for maximum c omfort and savings
  • 360° airflow reduces draft
  • Lower air velocities provide better airflow distribution
  • Condensate pump provided standard
  • Outside air integration possible
  • 10 year limited parts and compressor warranty

Benefits

N/A

  • Optional wired controller
  • Maximum piping length up to 164 ft. allows flexible placement of indoor unit
  • Maximum piping height separation up to 98 ft.
  • Low ambient cooling operation down to 0ºF (with optional wind baffle(s))