Print Back
Unit of Measure

Specifications

Model Type

N/A Round Flow Ceiling Cassette

Cooling Capacity

N/A 42000 Btu/h

Heating Capacity

N/A 47000 Btu/h

Optional Outside Air Intake Kit

N/A Yes

Fan Air Flow Rate

N/A 1220 ft³/min

Cooling Power Input

N/A 240 W

Heating Power Input

N/A 232 W

Sound Pressure Level

N/A 45 dBA

Outside Air Intake Kit Model

N/A KDDP55B160

Outside Air Intake Kit

N/A Yes

Power Supply

N/A 208/230 VAC, 60 Hz, 1 phase

Minimum Circuit Ampacity

N/A 1.5 A

Maximum Overcurrent Protection

N/A 15 A

Weight

N/A 25 kg55 lb

Dimensions

Depth

N/A 33-1/16 in840 mm

Width

N/A 33-1/16 in840 mm

Height

N/A 11-5/16 in287 mm

Pipe Connections - Liquid

N/A 3/8 in9.5 mm

Pipe Connections - Gas

N/A 5/8 in15.8 mm

Pipe Connections - Drain - External Diameter

N/A 1 1/4 in31.8 mm

Pipe Connections - Drain - Internal Diameter

N/A 1 in25.4 mm

System Efficiency Metrics

System Performance SEER

N/A 16

System Performance EER

N/A 10.2 Btu/h-W

System Performance HSPF

N/A 8.5

Features

N/A

  • 23 configurable airflow patterns ensure ideal air distribution for maximum c omfort and savings
  • 360° airflow reduces draft
  • Lower air velocities provide better airflow distribution
  • Condensate pump provided standard
  • Outside air integration possible
  • 10 year limited parts and compressor warranty

Benefits

N/A

  • Optional wired controller
  • Maximum piping length up to 164 ft. allows flexible placement of indoor unit
  • Maximum piping height separation up to 98 ft.
  • Low ambient cooling operation down to 0ºF (with optional wind baffle(s))