Print Back
Total comfort solution for heating, cooling, ventilation and controls.

Daikin’s VRV IV-X systems integrate advanced technology to provide comfort control to help maximize energy efficiency and reliability. VRV IV-X provides a solution for multi-family residential to large commercial applications desiring heating or cooling.

  • VRV with Variable Refrigerant Temperature (VRT) technology
  • Capacity range from 6 to 34 tons
  • 575V / 3ph / 60Hz
Unit of Measure

Specifications

Model Type

N/A Heat Pump

Fan Type

N/A Propellor Fan

Color

N/A Ivory White (5Y7.5/1)

Voltage

N/A 575 V

Phase

N/A 3

Frequency

N/A 60 Hz

Cooling Capacity

N/A 364000 Btu/h

Heating Capacity

N/A 432000 Btu/h126.6 kW

Compressor Type

N/A Hermetically Sealed Scroll

Compressor Displacement

N/A 24.37 + 24.68 + (16.27 + 17.54) m³/h

Fan Air Flow Rate

N/A 7989 + 7989 + 9480 ft³/min226 + 226 + 268 m³/min

Safety Devices

N/A High Pressure Switch, Fan Driver Overload Protector, Overcurrent Relay, Inverter Overload Protector

Weight

N/A 330 + 330 + 360 kg727 + 727 + 793 lb

Dimensions

Height 

N/A 66-11/16 + 66-11/16 + 66-11/16 in1694 + 1694 + 1694 mm

Width 

N/A 48-7/8 + 48-7/8 + 48-7/8 in1242 + 1242 + 1242 mm

Depth 

N/A 30-3/16 + 30-3/16 + 30-3/16 in767 + 767 + 767 mm

Pipe Connections - Gas

N/A 41.3 mm

System Efficiency Metrics

System Performance EER Non-Ducted

N/A 9.1

System Performance EER Ducted

N/A 9.1

System Performance Heating COP 17F Non-Ducted

N/A 2.06

System Performance Heating COP 17F Ducted

N/A 2.05

System Performance Heating COP 47F Ducted

N/A 3.2

System Performance Heating COP 47F Non-Ducted

N/A 3.32

System Performance IEER Ducted

N/A 15.6

System Performance IEER Non-Ducted

N/A 17

Features

N/A Features

  • Variable Refrigerant Temperature (VRT) control allows the VRV IV-X to deliver up to 28 % of improvement in seasonal cooling efficiency compared to previous Daikin VRV heat pump systems
  • Same product structure for 230 V and 460 V simplifies ordering
  • The rated seasonal cooling efficiency has been improved by an average of 11 % compared to VRV III
  • Improved efficiency with IEER values now up to 28
  • Larger capacity single modules ranging up to 14 tons and systems up to 34 tons allow for a more flexible system design
  • New configurator software designed to simplify the commissioning and maintenance of the system
  • Larger capacity single modules allow for opportunity to reduce electrical connections, piping connections and outdoor unit mounting fixtures
  • System wide auto-climate adjustment technology to increase the energy efficiency
  • All inverter compressors to increase the efficiency and avoid starting current inrush
  • Assembled in the US to increase flexibility and reduce lead times
  • Standard Limited Warranty: 10-year warranty on compressor and all parts
  • Factory standard coil guards

Benefits

N/A Benefits

  • 3 row 7mm heat exchanger coil improves efficiency
  • Inverter control board cooled by refrigerant to avoid influence from abient temperatures
  • Heat exchanger coil wraps around on all 4 sides of the unit to increase the surface area / efficiency
  • Designed with reduced MOP to optimize installation cost
  • Digital display on the unit for improved and faster configuration, commissioning, and trouble shooting.

Notes

Heating Capacity Note

N/A Indoor temp.: 70 ºFDB (21.1 ºCDB) / outdoor temp.: 47 ºFDB (8.3 ºCDB), 43 ºFWB (6.1 ºCWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).

Cooling Capacity Note

N/A Indoor temp.: 80 ºFDB (26.7 ºCDB), 67 ºFWB (19.4 ºCWB) / outdoor temp.: 95 ºFDB (35.0 ºCDB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m).