Daikin’s VRV IV systems integrate advanced technology to provide comfort control to help maximize energy efficiency and reliability. VRV IV provides a solution for multi-family residential to large commercial applications desiring heating or cooling. The VRV IV is the first variable refrigerant flow (VRF) system to be assembled in North America.
Model Type |
N/A Heat Recovery |
Fan Type |
N/A Propellor Fan |
Heat Exchanger Type |
N/A Cross Fin Coil |
Color |
N/A Ivory White (5Y7.5/1) |
Voltage |
N/A 575 V |
Phase |
N/A 3 |
Cooling Capacity |
N/A 120000 Btu/h |
Heating Capacity |
N/A 135000 Btu/h39.6 kW |
Compressor Type |
N/A Hermetically Sealed Scroll |
Compressor Displacement |
N/A 23.4 m³/h |
Fan Air Flow Rate |
N/A 7989 ft³/min226 m³/min |
Safety Devices |
N/A High Pressure Switch, Fan Driver Overload Protector, Overcurrent Fuse, Inverter Overload Protector, Leak Detecting Device |
Weight |
N/A 330 kg727 lb |
Height |
N/A 66-11/16 in1694 mm |
Width |
N/A 48-7/8 in1242 mm |
Depth |
N/A 30-3/16 in767 mm |
Pipe Connections - High/Low Pressure Gas |
N/A 3/4 in19.1 mm |
System Performance IEER Ducted |
N/A 19.60 |
System Performance SCHE Ducted |
N/A 22.20 |
System Performance Heating COP Ducted |
N/A 3.51 |
System Performance Heating COP 17F Ducted |
N/A 2.28 |
N/A
|
N/A
|
Cooling Capacity Note |
N/A Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft. (7.6 m), level difference: 0 ft. (0 m). |
Heating Capacity Note |
N/A Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft. (7.6 m), level difference: 0 ft. (0 m). |