Daikin’s VRV IV systems integrate advanced technology to provide comfort control to help maximize energy efficiency and reliability. VRV IV provides a solution for multi-family residential to large commercial applications desiring heating or cooling. The VRV IV is the first variable refrigerant flow (VRF) system to be assembled in North America.
Model Type |
N/A Heat Recovery |
Fan Type |
N/A Propellor Fan |
Heat Exchanger Type |
N/A Cross Fin Coil with Ultra Gold Corrosion Resistant Fin Coating |
Color |
N/A Ivory White (5Y7.5/1) |
Voltage |
N/A 208/230 V |
Phase |
N/A 3 |
Cooling Capacity |
N/A 312000 Btu/h |
Heating Capacity |
N/A 351000 Btu/h102.9 kW |
Compressor Type |
N/A Hermetically Sealed Scroll |
Compressor Displacement |
N/A (11.0 + 16.5) x 2 m³/h |
Fan Air Flow Rate |
N/A 8228 + 8228 ft³/min233 + 233 m³/min |
Safety Devices |
N/A High Pressure Switch, Fan Driver Overload Protector, Overcurrent Relay, Inverter Overload Protector |
Weight |
N/A 354 + 354 kg780 + 780 lb |
Height |
N/A 66-11/16 + 66-11/16 in1694 + 1694 mm |
Width |
N/A 48-7/8 + 48-7/8 in1242 + 1242 mm |
Depth |
N/A 30-3/16 + 30-3/16 in767 + 767 mm |
Pipe Connections - Gas |
N/A 34.9 mm |
Pipe Connections - High/Low Pressure Gas |
N/A 1-1/8 in28.6 mm |
System Performance IEER Ducted |
N/A 18.1 |
System Performance SCHE Ducted |
N/A 20.70 |
System Performance Heating COP Ducted |
N/A 3.20 |
System Performance Heating COP 17F Ducted |
N/A 2.11 |
N/A
Features |
N/A
Benefits |
Cooling Capacity Note |
N/A Indoor temp.: 80 ºFDB (26.7 ºCDB), 67 ºFWB (19.4 ºCWB) / outdoor temp.: 95 ºFDB (35.0 ºCDB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m). |
Heating Capacity Note |
N/A Indoor temp.: 70 ºFDB (21.1 ºCDB) / outdoor temp.: 47 ºFDB (8.3 ºCDB), 43 ºFWB (6.1 ºCWB) / Equivalent piping length: 25 ft (7.6 m), level difference: 0 ft (0 m). |