Family

N/A FXZQ

Cooling Capacity

N/A 9500 Btu/h2.8 kW

Heating Capacity

N/A 10500 Btu/h3.1 hp3.1 kW

Casing

N/A Galvanized steel plate

Coil (Cross Fin Coil) - Rows x Stages x FPI

N/A 2 x 12 x 22

Fan Model

N/A QTS32D15M

Fan Type

N/A Turbo Fan

Fan Motor Output

N/A 50 W

Fan Air Flow Rate

N/A 317 ft³/min

Fan Drive

N/A Direct Drive

Temperature Control

N/A Microprocessor thermostat for cooling and heating

Safety Devices

N/A PC board fuse

Refrigerant Control

N/A Electronic Expansion Valve

Connectable Outdoor Unit

N/A R410A VRV series

Decoration Panel Color

N/A White

Power Supply

N/A 208/230V 60Hz Single phase

Minimum Circuit Ampacity

N/A 0.3 A

Maximum Overcurrent Protection

N/A 15 A

Weight

N/A 35.3 lb16 kg

Dimensions

Width

N/A 22-5/8 in575 mm

Depth

N/A 22-5/8 in575 mm

Height 

N/A 10-1/4 (11-3/4) in260 (298) mm

Pipe Connections - Liquid

N/A 1/4 in6.4 mm

Pipe Connections - Gas

N/A 1/2 in12.7 mm

Pipe Connections - Drain - External Diameter

N/A 1 1/32 in26 mm

Pipe Connections - Drain - Internal Diameter

N/A 25/32 in20 mm

Application

N/A

  • Retail
  • Schools
  • Offices

Features

N/A

The VISTA™ 2x2 Cassette Unit for VRV systems seamlessly integrates into 2x2 ceiling grids with a remarkable blend of iconic design and engineering excellence.

  • Redesigned decoration panel eliminates overlap of adjacent tiles and simplifies coordination
  • Low profile panel design measures a mere 5/16” (8mm) deep
  • Incorporation of DC fan motor reduces operational power input up to 48%*
  • Independently motorized louvers allow for greater air distribution flexibility
  • 4-way, 3-way, and 2-way blow configurability
  • Auto** fan speed control optimizes fan energy input by intelligently controlling fan speed
  • Configurable auxiliary heat control allows for high degree of control of heater on/off temperatures
  • Direct integration of outside air
  • The decoration panel is available in white (BYFQ60C3W1W), or silver/white (BYFQ60C3W1S)
  • Backed by 10 year parts limited warranty***
    • *When compared vs previous generation FXZQ_MVJU9
      **Requires BRC1E73 or iTouch Manager
      ***Complete warranty details available from local distributor or manufacturer’s representative

    Benefits

    N/A

    An optional space and presence sensor kit (BRYQ60A2W / BRYQ60A2S) can be installed to further enhance operational efficiency and occupant comfort.

  • Senses occupancy and sets the unit to a more efficient set point after the space has been unoccupied for 30 minutes (adjustable) or more
  • Can be configured to automatically turn the unit Off after 2 hours (adjustable) when no occupancy is detected
  • Detects location of occupants near the unit and automatically adjusts louver airflow direction to reduce uncomfortable drafts
  • Presence sensor sensitivity is adjustable
  • Floor temperature sensors will automatically adjust louver airflow direction to maintain an even and comfortable temperature distribution from floor to ceiling*
    • *The presence sensor will always take precedence over floor sensor

    Notes

    Heating Capacity Note

    N/A

    Nominal heating capacities are based on the following conditions:

    • Return air temperature: 70.0 °F DB (21.1 °C DB)
    • Outdoor temperature: 47.0 °F DB (8.3 °C DB), 43.0 °F WB (6.1 °C WB)
    • Equivalent ref. piping length: 25 ft (7. 6 m) (Horizontal)

    Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

    Cooling Capacity Note

    N/A

    Nominal cooling capacities are based on the following conditions:

    • Return air temperature: 80.0 °F DB (26.7 °C DB), 67.0 °FWB (19.4 °C WB)
    • Outdoor temperature: 95.0 °F DB (35.0 °C DB)
    • Equivalent ref. piping length: 25 ft (7. 6 m) (Horizontal)

    Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.