Energy recovery ventilator
The VAM is designed to efficiently maintain indoor air quality br providing sufficient levels of outside air while recovering waste energy from the exhaust air leaving the conditioned zone.
Family |
N/A VAM |
Model Type |
N/A Ducted |
Fan Air Flow Rate |
N/A 470 ft³/min |
Temperature Recovery Efficiency - Cooling |
N/A 68 % |
Temperature Recovery Efficiency - Heating |
N/A 66 % |
Enthalpy Recovery Efficiency - Cooling |
N/A 45 % |
Enthalpy Recovery Efficiency - Heating |
N/A 59 % |
External Static Pressure |
N/A 0.73 inWc |
Sound Pressure Level |
N/A 42.0 dBA |
Power Supply |
N/A 208-230 V/ 60 Hz / 1 Phase |
Minimum Circuit Ampacity |
N/A 3.9 A |
Maximum Overcurrent Protection |
N/A 15 A |
Voltage |
N/A 208-230 V |
Phase |
N/A 1 |
Frequency |
N/A 60 Hz |
Weight |
N/A 121 lb |