  • Capacity range from 3 to 6 tons
  • Numerous voltages and phases for application flexibility
  • All units has a choice of 3-phase 208/230V, 460V or 575V
  • 3-5 ton units also have a choice of 1-phase 208/230V
  • All models have ECM Direct-Drive Indoor Fan Motor
  • Designed to fit standard curb sizes for ease of many replacements
Unit of Measure

Specifications

Cooling Capacity

N/A 69000 Btu/h6 TR

IEER

N/A 17

EER

N/A 11.5

Heating Capacity

N/A 62000 Btu/h

COP

N/A 3.40

Operating Weight

N/A 708 lb

Shipping Weight

N/A 766 lb

Evaporator Motor / Coil

Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 12 x 11 in

Indoor Nominal CFM

N/A 2200

Evaporator Motor - RPM

N/A 1500

Evaporator Motor Horsepower

N/A 1.2 hp

Filter Size

N/A 20 x 20 x 2 (4) in

Drain Size (NPT)

N/A 3/4 in

R410A Refrigerant Charge

N/A 304 oz

Evaporator Coil Face Area

N/A 10.1 ft²

Rows Deep

N/A 4

Fins per Inch

N/A 16

Condenser Fan / Coil

Outdoor Horsepower

N/A 1

RPM (High/Low stage)

N/A 1122

Outdoor Horsepower

N/A 0.33 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 4

Condenser Coil Face Area

N/A 24.5 ft²

Rows Deep

N/A 2

Fins per Inch

N/A 16

Compressor

Quantity

N/A 1

Type

N/A Scroll

Stage

N/A 2

Rated Load Amps

N/A 17.6 A

Locked Rotor Amps

N/A 136 A

Electrical Data

Voltage

N/A 208-230 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 5.0 A

Max External Static

N/A 0.75 inWc

Outdoor Fan FLA

N/A 2 A

Min. Circuit Ampacity

N/A 29.0/29.0 A

Max. Overcurrent Protection

N/A 45/45 A

Dimensions

Depth

N/A 74 in

Width

N/A 48-5/16 in

Height