Print Back
Unit of Measure

Specifications

Condenser Fan Motor Horsepower

N/A 1/4 hp

Voltage

N/A 208-230 V

Cooling Capacity

N/A 60000 Btu/h

Nominal Cooling Capacity (Tons)

N/A 5

Sound Level

N/A 72 dB

Compressor Rated Load Amps

N/A 16.0 A

Compressor Locked Rotor Amps

N/A 110.0 A

Condenser Fan Motor Full Load Amps

N/A 1.50 A

Valve Type

N/A Sweat

Refrigerant Charge

N/A 130 oz

Piston Size

N/A 0.086

Phase

N/A 3

Minimum Circuit Ampacity

N/A 21.5 A

Maximum Overcurrent Protection

N/A 35 A

Min/Max Volts

N/A 197/253 V

Series

N/A DX13S

Refrigerant Used

N/A R-410A

Shipping Weight

N/A 301 lb

Dimensions

Depth

N/A 35 1/2 in

Width

N/A 35 1/2 in

Height

N/A 38-1/4 in

Liquid Line Size O.D.

N/A 3/8 in

Suction Line Size O.D.

N/A 1 1/8 in

Liquid Valve Size O.D.

N/A 3/8 in

Suction Valve Size O.D.

N/A 7/8 in

Electrical Conduit Size

N/A 1/2 or 3/4 in

Parallel Unit Minimum Clearance

N/A 24 in

Unit Minimum Clearance

N/A 12 in

Unit Top Minimum Clearance

N/A 60 in

Lower Access Panel Depth

N/A 4 in

Lower Access Panel Height

N/A 17 in

Lower Access Panel Width

N/A 7 in

System Efficiency Metrics

System Performance SEER

N/A 13

Features

N/A Standard Features

  • Energy-efficient compressor
  • Factory-installed filter drier
  • Copper tube/ enhanced aluminum fin coil
  • Service valves with sweat connections and easy-access gauge ports
  • Contactor with lug connection
  • Ground lug connection
  • Units meet the performance outlined in Table 6.8.1B of ASHRAE Standard 90.1-2010
  • AHRI Certified
  • ETL Listed
Cabinet Features
  • Innovative louvered sound control top design
  • Steel louver coil guard
  • Heavy-gauge galvanized-steel cabinet
  • Attractive Nickel Gray powder-paint finish
  • Top and side maintenance access
  • Single-panel access to controls with space provided for field-installed accessories
  • When properly anchored, meets the 2010 Florida Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)