Print Back
12 1/2 Ton AC Direct Drive 3 Phase 575V
Unit of Measure

Specifications

Type

N/A Light Commercial Packaged Air Conditioner

Cooling Capacity

N/A 140000 Btu/h12 1/2 T

IEER

N/A 14.4

System Performance EER

N/A 11

AHRI Reference #

N/A 210240237

Sound Level

N/A 86.8 dB

Operating Weight

N/A 1150 lb

Shipping Weight

N/A 1230 lb

Evaporator Motor / Coil

Evaporator Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 15x15 in

Indoor Nominal CFM

N/A 4200

RPM

N/A 300-1600

Evaporator Motor Horsepower

N/A 3.5 hp

Filter Size

N/A 20 x 25 x 2 (2) in25 x 25 x 2 (2) in

Drain Size (NPT)

N/A 3/4 in

R-410A Refrigerant Charge

N/A 148/142 oz

Evaporator Coil Face Area

N/A 16.2 ft²

Rows Deep

N/A 4

Fins per Inch

N/A 16

Condenser Fan / Coil

Quantity of Condenser Fan Motors

N/A 2

RPM (High/Low stage)

N/A 1075

Outdoor Horsepower

N/A 1/2 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 40.8 ft²

Rows Deep

N/A 1

Fins per Inch

N/A 23

Compressor

Quantity

N/A 2

Type

N/A Scroll

Rated Load Amps

N/A 7.4 A

Locked Rotor Amps

N/A 50 A

Electrical Data

Voltage

N/A 575 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 5.0 A

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 1 A

Min. Circuit Ampacity

N/A 23.7 A

Max. Overcurrent Protection

N/A 30 A

Power Supply Conduit Hole Diameter

N/A 1.375 in

Low-Voltage Conduit Hole Diameter

N/A 0.5 in

Dimensions

Depth

N/A 93-3/4 in

Width

N/A 60-3/8 in

Height

N/A 54-5/8 in

Features and Benefits

N/A Installation
Daikin Packaged units are designed with fast and easy installation in mind and are ideal for both new construction and retrofit projects. Our packaged rooftop units are built to be a direct replacement for most rooftop units in the field without the need of a curb adapter

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors to match the required total load.

Supply Fan
Indoor forward curved fan, paired with direct-drive motor, provide for easy airflow control.

Coils
All units use large face area outdoor coils. These coils are constructed with microchannel technology for high operating efficiencies.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use weatherproof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and long lasting component maintenance.

Heating Section
Wide range of electric heat selections effectively handle most comfort heating demand from morning warm-up control to full heat.

Electric Heat
ETL approved electric heat is factory assembled, installed and tested.

Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.