Print Back
5 Ton Gas/Electric Direct Drive 3 Phase 208-230V
Unit of Measure

Specifications

Type

Light Commercial Packaged Gas/Electric

Cooling Capacity

59000 Btu/h5 T

SEER

14.0

EER

11.5

SEER2

13.4

EER2

11.0

AHRI Reference #

207516915

Sound Level

78.3 dB

Operating Weight

554 lb

Shipping Weight

624 lb

Heating Capacity

Heating Capacity

140000 Btu/h

Heat Range

High

No. of Burners

6

High Stage Input

140 Btu/h

High Stage Output

112 Btu/h

Low Stage Input

105 Btu/h

Low Stage Output

84 Btu/h

Thermal Efficiency

80

High Stage Temperature Rise Range

35 to 65 ºF

Low Stage Temperature Rise Range

30 to 60 ºF

Evaporator Motor / Coil

Evaporator Motor Type

Direct Drive

External Static Pressure (ESP)

Standard

Wheel Dia. x Width

12 X 11 in

Indoor Nominal CFM

1820

RPM

1200/VAR

Evaporator Motor Horsepower

1.0 hp

Filter Size

20 x 25 x 2 (2) in

Drain Size (NPT)

3/4 in

R-410A Refrigerant Charge

82 oz

Evaporator Coil Face Area

6.41 ft²

Rows Deep

3

Fins per Inch

16

Condenser Fan / Coil

Quantity of Condenser Fan Motors

1

RPM (High/Low stage)

1122

Outdoor Horsepower

1/3 hp

Diameter

22 in

No. of Fan Blades

3

Condenser Coil Face Area

17.6 ft²

Rows Deep

1

Fins per Inch

23

Compressor

Quantity

1

Type

Scroll

Stage

1

Rated Load Amps

16.0 A

Locked Rotor Amps

110.0 A

Electrical Data

Voltage

208 to 230 V

Number of Phases

3

Frequency

60 Hz

Indoor Blower FLA

6.9 A

Max External Static

0.8 inWc

Outdoor Fan FLA

2 A

Min. Circuit Ampacity

28.9/28.9 A

Max. Overcurrent Protection

40/40 A

Power Supply Conduit Hole Diameter

1.125 in

Low-Voltage Conduit Hole Diameter

0.5 in

Dimensions

Depth

74 in

Width

48-5/16 in

Height

39 7/8 in

Features and Benefits

N/A Installation
Daikin Packaged units are designed with an easier and faster installation in mind for both new construction and retrofit. Our packaged rooftop units are built to be a direct replacement for most rooftop units on the field without the need of a curb adapter, to be able to replace the unit in a shorter time and at a lower expense.

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors to match the required total load for efficient part load control.

Supply Fan
The direct drive with airfoil single width, single inlet (SWSI) Class II construction supply fan with aluminum fan +blades provides efficient and quiet operation at wide ranging static pressure and air flow requirements.

Coils
All units use large face area outdoor coils. These coils are constructed with seamless copper tubes, mechanically bonded into aluminum plate-type fins with full drawn collars to completely cover the tubes for high operating efficiencies.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use, weather proof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and longer lasting component maintenance.

Heating Section
Wide range of natural gas selections effectively handle most comfort heating demand from morning warm-up control to full heat, all available with Daikin’s Wrinkle Bend heat exchanger technology.

Gas Furnace
ETL certified heating modules provide a custom match to specific design requirement.

Electrical
Units are completely wired and tested at the factory to provide faster commissioning and start-up.