The DSH Packaged Heat Pumps units are built to perform, with features and options that help provide lower installation and operating costs, superior indoor air quality, quiet operation, and longevity.
Unit of Measure

Specifications

Model Type

Heat Pump

Sound Level

82 dBA

Operating Weight

649 lb

Ship Weight

719 lb

Cooling Capacity

Cooling Capacity

68000 Btu/h

SEER2

16.7

EER2

11.3

IEER

16.70

EER

11.30

Heating Capacity

Heating Capacity

67000 Btu/h

COP @47

3.4

COP @17

2.25

Evaporator Motor / RTPF (Round Tube Plate Fin)

Motor Type

Direct Drive

External Static Pressure (ESP)

High

Wheel Dia. X Width

12 X 11 in

Indoor Nominal CFM

2380 ft³/min

RPM

300 - 1500 rpm

Indoor Horsepower

2.30

Filter Size

14 X 20 X 2 (2) 20 X 20 X 2 (2)

Drain Size (NPT)

3/4

R-32 Refrigerant Charge Circuit No. 1

182 oz

Evaporator Coil Face Area

9.16 ft²

Rows Deep / Fins per Inch

4/16

Condenser Fan / MCHX (Microchannel heat exchanger)

Quantity of Condenser Fan Motors

1

RPM

1115

Outdoor Horsepower

1/2 hp

Fan Diameter

22 in

# Fan Blades

3

Face Area

19.01 ft²

Rows Deep / Fins per Inch

2 / 20

Compressor

Quantity

1

Type

Scroll

Stages

2

Compressor RLA / LRA

7.0 / 70.8

Electrical Data

Voltage

460 V

Phase

3

Frequency

60 Hz

Indoor Blower FLA

4.5

Max External Static

1.6 inWc

Outdoor Fan FLA

1.4

Min. Circuit Ampacity

14.7

Max. Overcurrent Protection

20 A

Power Supply Conduit Hole Dia.

1.125 in

Low-Voltage Conduit Hole Dia.

0.5 in

Dimensions

Depth

47 5/8 in

Width

73 3/8 in

Height

43 1/2 in