  • Capacity range from 3 to 6 tons
  • Numerous voltages and phases for application flexibility
  • All units has a choice of 3-phase 208/230V, 460V or 575V
  • 3-5 ton units also have a choice of 1-phase 208/230V
  • All models have ECM Direct-Drive Indoor Fan Motor
  • Designed to fit standard curb sizes for ease of many replacements
Unit of Measure

Specifications

Cooling Capacity

48000 Btu/h4 T

SEER

17

EER

12.6

Heating Capacity

47000 Btu/h

HSPF

8.2

Sound Level

73.0 dB

Operating Weight

621 lb

Shipping Weight

679 lb

Evaporator Motor / Coil

Motor Type

Direct Drive

External Static Pressure (ESP)

Standard

Wheel Dia. x Width

12 X 11 in

Indoor Nominal CFM

1600

Evaporator Motor - RPM

1200

Evaporator Motor Horsepower

1.0 hp

Filter Size

14 x 20 x 2 (4) in

Drain Size (NPT)

3/4 in

R410A Refrigerant Charge

196 oz

Evaporator Coil Face Area

7.3 ft²

Rows Deep

4

Fins per Inch

16

Condenser Fan / Coil

Outdoor Horsepower

1

RPM (High/Low stage)

1050/700

Outdoor Horsepower

0.33 hp

Diameter

22 in

No. of Fan Blades

3

Condenser Coil Face Area

19.3 ft²

Rows Deep

2

Fins per Inch

16

Compressor

Quantity

1

Type

Scroll

Stage

2

Rated Load Amps

21.2 A

Locked Rotor Amps

104 A

Electrical Data

Voltage

208-230 V

Number of Phases

1

Frequency

60 Hz

Indoor Blower FLA

6.9 A

Max External Static

0.75 inWc

Outdoor Fan FLA

3.5 A

Min. Circuit Ampacity

36.8/36.8 A

Max. Overcurrent Protection

50/50 A

Power Supply Conduit Hole Diameter

1.125 in

Low-Voltage Conduit Hole Diameter

0.5 in

Dimensions

Depth

74 in

Width

48-5/16 in

Height

43 1/2 in