Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
The DSH Packaged Heat Pumps units are built to perform, with features and options that help provide lower installation and operating costs, superior indoor air quality, quiet operation, and longevity.
Unit of Measure

Model Type

N/A Heat Pump

Sound Level

N/A 79 dBA

Operating Weight

N/A 600 lb

Ship Weight

N/A 670 lb

Cooling Capacity

N/A 57500 Btu/h

SEER2

N/A 13.7

EER2

N/A 11.8

Heating Capacity

N/A 55000 Btu/h

HSPF2

N/A 6.90

Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. X Width

N/A 12 X 11 in

Indoor Nominal CFM

N/A 1870 ft³/min

RPM

N/A 300 - 1500 rpm

Indoor Horsepower

N/A 1.20

Filter Size

N/A 14 X 20 X 2 (4)

Drain Size (NPT)

N/A 3/4

R-32 Refrigerant Charge Circuit No. 1

N/A 163 oz

Evaporator Coil Face Area

N/A 7.33 ft²

Rows Deep / Fins per Inch

N/A 4/16

Quantity of Condenser Fan Motors

N/A 1

RPM

N/A 1050

Outdoor Horsepower

N/A 1/3 hp

Fan Diameter

N/A 22 in

# Fan Blades

N/A 4

Face Area

N/A 17.28 ft²

Rows Deep / Fins per Inch

N/A 2 / 20

Quantity

N/A 1

Type

N/A Scroll

Stages

N/A 1

Compressor RLA / LRA

N/A 7.7 / 58.1

Voltage

N/A 460 V

Phase

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 2.5

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 0.85

Min. Circuit Ampacity

N/A 13.0

Max. Overcurrent Protection

N/A 20 A

Power Supply Conduit Hole Dia.

N/A 1.125 in

Low-Voltage Conduit Hole Dia.

N/A 0.5 in

Depth

N/A 47 5/8 in

Width

N/A 73 3/8 in

Height

N/A 39 7/8 in