Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
The DSH Packaged Heat Pumps units are built to perform, with features and options that help provide lower installation and operating costs, superior indoor air quality, quiet operation, and longevity.
Unit of Measure

Model Type

N/A Heat Pump

Sound Level

N/A 83.7 dBA

Operating Weight

N/A 1157 lb

Ship Weight

N/A 1229 lb

Cooling Capacity

N/A 98000 Btu/h

IEER

N/A 15.5

EER

N/A 11.4

Heating Capacity

N/A 97000 Btu/h

COP @47

N/A 3.4

COP @17

N/A 2.25

Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. X Width

N/A 15 X 12 in

Indoor Nominal CFM

N/A 3400 ft³/min

RPM

N/A 300 - 1600 rpm

Indoor Horsepower

N/A 2.4

Filter Size

N/A 20 X 25 X 2 (2) 25 X 25 X 2 (2)

Drain Size (NPT)

N/A 3/4

R-32 Refrigerant Charge Circuit No. 1

N/A 152 oz

R-32 Refrigerant Charge Circuit No. 2

N/A 152 oz

Evaporator Coil Face Area

N/A 15 ft²

Rows Deep / Fins per Inch

N/A 3 / 16

Quantity of Condenser Fan Motors

N/A 2

RPM

N/A 1122

Outdoor Horsepower

N/A 1/3 hp

Fan Diameter

N/A 22 in

# Fan Blades

N/A 3

Face Area

N/A 33.3 ft²

Rows Deep / Fins per Inch

N/A 2/16

Quantity

N/A 2

Type

N/A Scroll

Stages

N/A 1

Compressor RLA / LRA

N/A 14.1/120

Voltage

N/A 208/230 V

Phase

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 8

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 2.7

Min. Circuit Ampacity

N/A 43.7

Max. Overcurrent Protection

N/A 50 A

Power Supply Conduit Hole Dia.

N/A 1.375 in

Low-Voltage Conduit Hole Dia.

N/A 0.5 in

Depth

N/A 59 5/8 in

Width

N/A 93 1/8 in

Height

N/A 54 5/8 in

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.