Print Back
The DSH Packaged Heat Pumps units are built to perform, with features and options that help provide lower installation and operating costs, superior indoor air quality, quiet operation, and longevity.
Unit of Measure

Specifications

Model Type

Heat Pump

Sound Level

75 dBA

Operating Weight

543 lb

Ship Weight

613 lb

Cooling Capacity

Cooling Capacity

35000 Btu/h

SEER2

14

EER2

12

Heating Capacity

Heating Capacity

33600 Btu/h

HSPF2

6.90

Evaporator Motor / RTPF (Round Tube Plate Fin)

Motor Type

Direct Drive

External Static Pressure (ESP)

Standard

Wheel Dia. X Width

12 X 11 in

Indoor Nominal CFM

1220 ft³/min

RPM

300 - 1500 rpm

Indoor Horsepower

1.20

Filter Size

14 X 20 X 2 (4)

Drain Size (NPT)

3/4

R-32 Refrigerant Charge Circuit No. 1

140 oz

Evaporator Coil Face Area

7.33 ft²

Rows Deep / Fins per Inch

3/16

Condenser Fan / MCHX (Microchannel heat exchanger)

Quantity of Condenser Fan Motors

1

RPM

810

Outdoor Horsepower

1/6 hp

Fan Diameter

22 in

# Fan Blades

3

Face Area

12.67 ft²

Rows Deep / Fins per Inch

2 / 16

Compressor

Quantity

1

Type

Scroll

Stages

1

Compressor RLA / LRA

4.9 / 44.3

Electrical Data

Voltage

460 V

Phase

3

Frequency

60 Hz

Indoor Blower FLA

2.5

Max External Static

0.8 inWc

Outdoor Fan FLA

0.48

Min. Circuit Ampacity

9.1

Max. Overcurrent Protection

15 A

Power Supply Conduit Hole Dia.

1.125 in

Low-Voltage Conduit Hole Dia.

0.5 in

Dimensions

Depth

47 5/8 in

Width

73 3/8 in

Height

39 7/8 in