Print Back
The DSH Packaged Heat Pumps units are built to perform, with features and options that help provide lower installation and operating costs, superior indoor air quality, quiet operation, and longevity.
Unit of Measure

Specifications

Model Type

N/A Heat Pump

Sound Level

N/A 82 dBA

Operating Weight

N/A 649 lb

Ship Weight

N/A 719 lb

Cooling Capacity

Cooling Capacity

N/A 68000 Btu/h

SEER2

N/A 16.7

EER2

N/A 11.3

IEER

N/A 16.70

EER

N/A 11.30

Heating Capacity

Heating Capacity

N/A 67000 Btu/h

COP @47

N/A 3.4

COP @17

N/A 2.25

Evaporator Motor / RTPF (Round Tube Plate Fin)

Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A High

Wheel Dia. X Width

N/A 12 X 11 in

Indoor Nominal CFM

N/A 2380 ft³/min

RPM

N/A 300 - 1500 rpm

Indoor Horsepower

N/A 2.30

Filter Size

N/A 14 X 20 X 2 (2) 20 X 20 X 2 (2)

Drain Size (NPT)

N/A 3/4

R-32 Refrigerant Charge Circuit No. 1

N/A 182 oz

Evaporator Coil Face Area

N/A 9.16 ft²

Rows Deep / Fins per Inch

N/A 4/16

Condenser Fan / MCHX (Microchannel heat exchanger)

Quantity of Condenser Fan Motors

N/A 1

RPM

N/A 1115

Outdoor Horsepower

N/A 1/2 hp

Fan Diameter

N/A 22 in

# Fan Blades

N/A 3

Face Area

N/A 19.01 ft²

Rows Deep / Fins per Inch

N/A 2 / 20

Compressor

Quantity

N/A 1

Type

N/A Scroll

Stages

N/A 2

Compressor RLA / LRA

N/A 7.0 / 70.8

Electrical Data

Voltage

N/A 460 V

Phase

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 4.5

Max External Static

N/A 1.6 inWc

Outdoor Fan FLA

N/A 1.4

Min. Circuit Ampacity

N/A 14.7

Max. Overcurrent Protection

N/A 20 A

Power Supply Conduit Hole Dia.

N/A 1.125 in

Low-Voltage Conduit Hole Dia.

N/A 0.5 in

Dimensions

Depth

N/A 47 5/8 in

Width

N/A 73 3/8 in

Height

N/A 43 1/2 in