Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
- Capacity range from 3 to 12.5 tons
- Numerous voltages and phases for application flexibility
- All units has a choice of 3-phase 208/230V, 460V or 575V
- 3-5 ton units also have a choice of 1-phase 208/230V
- All models have ECM Direct-Drive Indoor Fan Motor
- Designed to fit standard curb sizes for ease of many replacements
Unit of Measure
Cooling Capacity |
N/A 137000 Btu/h12-1/2 TR |
IEER |
N/A 16 |
EER |
N/A 11.7 |
Sound Level |
N/A 80.5 dB |
Operating Weight |
N/A 1195 lb |
Shipping Weight |
N/A 1270 lb |
Motor Type |
N/A Direct |
External Static Pressure (ESP) |
N/A 0.8 IN.W.G. |
Wheel Dia. x Width |
N/A 15.12 x 15.00 in |
Indoor Nominal CFM |
N/A 3800 |
Evaporator Motor - RPM |
N/A 1300 |
Evaporator Motor Horsepower |
N/A 3.5 hp |
Filter Size |
N/A 25 x 25 x 2 (4) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 190/188 oz |
Evaporator Coil Face Area |
N/A 19.1 ft² |
Rows Deep |
N/A 4 |
Fins per Inch |
N/A 16 |
Outdoor Horsepower |
N/A 2 |
RPM (High/Low stage) |
N/A 1122 |
Outdoor Horsepower |
N/A 1/3 hp |
Diameter |
N/A 22 in |
No. of Fan Blades |
N/A 3 |
Condenser Coil Face Area |
N/A 43.8 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 28 |
Quantity |
N/A 2 |
Type |
N/A Scroll |
Stage |
N/A 1 |
Rated Load Amps |
N/A 19 A |
Locked Rotor Amps |
N/A 123 A |
Voltage |
N/A 208-230 V |
Number of Phases |
N/A 3 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 10.9 A |
Max External Static |
N/A 0.8 inWc |
Outdoor Fan FLA |
N/A 2 A |
Min. Circuit Ampacity |
N/A 60.7/60.7 A |
Max. Overcurrent Protection |
N/A 70/70 A |
Power Supply Conduit Hole Diameter |
N/A 1.375 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.375 in |
Depth |
N/A 93-3/4 in |
Width |
N/A 60-3/8 in |
Height |
N/A 58-3/5 in |