Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
Ceiling mounted, one way blow cassette unit

A compact design and single-way air disribution make this unit ideal for installation in the tightest of spaces.

  • Capacity range from 7.5 MBH to 24 MBH
  • Requires less than 10" of ceiling space clearance for installation.
  • Utilization of a DC-style fan motor and integral condensate pump allow for improvements in energy consumption as well as low operating sound levels.
Unit of Measure

Family

N/A FXEQ

Model Type

N/A One Way Blow Cassette

Cooling Capacity

N/A 9500 Btu/h

Heating Capacity

N/A 10500 Btu/h3.1 kW

Fan Air Flow Rate

N/A 244 ft³/min

Sound Pressure Level

N/A 35 dBA

Power Supply

N/A 208/230 V, 60 Hz, 1 phase

Minimum Circuit Ampacity

N/A 0.40 A

Maximum Overcurrent Protection

N/A 15 A

Voltage

N/A 208/230 V

Frequency

N/A 60 Hz

Weight

N/A 17 kg37.5 lb

Height

N/A 7-7/8 in200 mm

Width

N/A 18-1/2 in470 mm

Depth

N/A 33-1/16 in840 mm

Pipe Connections - Liquid

N/A 1/4 in6.4 mm

Pipe Connections - Gas

N/A 1/2 in12.7 mm

Pipe Connections - Drain - External Diameter

N/A 1 1/32 in26 mm

Pipe Connections - Drain - Internal Diameter

N/A 13/16 in20 mm

N/A

  • Retail
  • Schools
  • Offices
  • Restaurants

N/A

  • Compact design with 7-7/8" body height and 3-3/16 panel height
  • Outside air integration ready (requires field supplied accessories)
  • Energy efficient fan with 5 speed settings
  • Mold resistant resin decoration panel that matches standard ceiling color

N/A

  • Increased overall heating effect due to the innovative discharge air louver design
  • Compact heat exchanged and fan design to increase space saving

Cooling Capacity Note

N/A Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0 ºFDB (26.7 ºCDB), 67.0 ºFWB (19.4 ºCWB)
Outdoor temperature: 95.0 ºFDB (35.0 ºCDB)
Equivalent ref. piping length: 25 ft (7.6 m) (Horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Heating Capacity Note

N/A Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0 ºFDB (21.1 ºCDB)
Outdoor temperature: 47.0 ºFDB (8.3.0 ºCDB), 43.0 ºFWB (6.1 ºCWB)
Equivalent ref. piping length: 25 ft (7.6 m) (Horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.