Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.

CAD CART (0)
  • Cart is empty
A modular, energy-efficient and reliable alternative to centralized equipment
Can be applied to both geothermal and boiler/tower applications as standard
  • Small condensers can be triple stacked for reduced installation space and increased usable square footage
  • VRV with Variable Refrigerant Temperature (VRT)
  • Refrigerant cooled inverter technology to deliver consistent and reliable PCB operations
  • Drop-down electrical box for easy service to key components
  • Field selectable top or front refrigerant connections for flexible and easy installation
  • 208-230V / 3ph / 60Hz (RWEQ_TATJU)
Unit of Measure

Model Type

N/A Heat Recovery

Heat Exchanger Type

N/A Stainless Steel Plate

Color

N/A Ivory White (5Y7.5/1)

Cooling Capacity

N/A 119.6 kW408000 Btu/h

Heating Capacity

N/A 459000 Btu/h134.5 kW

Power Supply

N/A 575 V, 60 Hz, 3 phase

Voltage

N/A 575 V

Phase

N/A 3

Frequency

N/A 60 Hz

Compressor Type

N/A Hermetically Sealed Scroll

Compressor Displacement

N/A 28.5 + 28.5 + 25.0 m³/h1,006 + 1,005 + 884 ft³/h

Safety Devices

N/A High Pressure Switch, Inverter Overload Protector, Fusible Plug, Leak Detecting Device, Overcurrent Fuse

Weight

N/A 200 + 200 + 200 kg440.9 + 440.9 + 440.9 lb

Height 

N/A (38-9/16) x 3 in(980) x 3 mm

Width 

N/A (30-1/8) x 3 in(765) x 3 mm

Depth 

N/A (22-1/16) x 3 in(560) x 3 mm

Pipe Connections - Gas

N/A 1-5/8 (41.3) C1220T (Brazing Connection) -Main Line-

Pipe Connections - Water Inlet

N/A ISO 228-1-G1 1/4B (External thread)

Pipe Connections - Water Outlet

N/A ISO 228-1-G1 1/4B (External thread)

System Performance IEER Ducted

N/A 17.2

System Performance IEER Non-Ducted

N/A 18.2

System Performance COP Ducted

N/A 4.35

System Performance Heating COP Non-Ducted

N/A 4.03

System Performance SCHE Ducted

N/A 18.50

System Performance SCHE Non-Ducted

N/A 21.20

N/A

  • Wide offering with 8, 10 and 12 ton single module and up to 36 tons with multi-module
  • Flexible System design with increased diversity up to 150%
  • Up to 50% and 38% reduction in space and weight respectively to install systems of similar capacity when compared to VRV-W _ PC series (Model spcific, check product specification for details)
  • Triple-stack capable to deliver up to 36 tons in 10.5 ft. ceiling height
  • Flexible and easy installation with field selectable top or front refrigerant connections
  • Design flexibility with long piping lengths up to 980 ft. total (540 ft. max. linear liquid piping length) and up to 100 ft. vertical separation between indoor units
  • Engineered with Patented heat rejection cancelation technology to eliminate mechanical room conditioning requirements

N/A

  • Year round comfort and energy efficiency by combining VRV and Variable Refrigerant Temperature (VRT) technologies
  • 0-10V variable water flow control logic as standard to increase waterside system operational efficiencies
  • Refrigerant cooled inverter technology to deliver consistent and reliable printed circuit board operations
  • Factory ships ready for Geothermal applications
  • Ease commissioning with ability to program settings off site using new configurator tool
  • 3-digit 7-segment digital display on the unit for improved and faster configuration, commissioning, and troubleshooting
  • Engineered for easy service with drop-down switch box to access key components
  • Seamless integration to full suite of Daikin Control Solutions for complete system control
  • Backed by 10 year parts limited warranty and 10 years replacement compressor limited warranty

Cooling Capacity Note

N/A Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB)/Inlet water temp.: 86°F (30°C). Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).

Heating Capacity Note

N/A Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB)/Inlet water temp.: 68°F (20°C). Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).

Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.