Print Back
4 Ton Gas/Electric Direct Drive Single Phase 208-230V
Unit of Measure

Specifications

Type

N/A Light Commercial Packaged Gas/Electric

Cooling Capacity

N/A 47000 Btu/h4 T

SEER2

N/A 13.4

EER2

N/A 11.0

AHRI Reference #

N/A 208120668

Sound Level

N/A 78.4 dB

Operating Weight

N/A 537 lb

Shipping Weight

N/A 607 lb

Heating Capacity

Heating Capacity

N/A 70000 Btu/h

Heat Range

N/A Low

No. of Burners

N/A 4

High Stage Input

N/A 90.0 Btu/h

High Stage Output

N/A 72.9 Btu/h

Annual Fuel Utilization Efficiency (AFUE)

N/A 81

High Stage Temperature Rise Range

N/A 25 to 55 ºF

Evaporator Motor / Coil

Evaporator Motor Type

N/A Direct Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 12 x 11 in

Indoor Nominal CFM

N/A 1570

RPM

N/A 1200/VAR

Evaporator Motor Horsepower

N/A 1.0 hp

Filter Size

N/A 20 x 25 x 2 (2) in

Drain Size (NPT)

N/A 3/4 in

R-410A Refrigerant Charge

N/A 79 oz

Evaporator Coil Face Area

N/A 6.41 ft²

Rows Deep

N/A 3

Fins per Inch

N/A 16

Condenser Fan / Coil

Quantity of Condenser Fan Motors

N/A 1

RPM (High/Low stage)

N/A 1122

Outdoor Horsepower

N/A 1/3 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 12.3 ft²

Rows Deep

N/A 1

Fins per Inch

N/A 23

Compressor

Quantity

N/A 1

Type

N/A Scroll

Stage

N/A 1

Rated Load Amps

N/A 19.9 A

Locked Rotor Amps

N/A 109 A

Electrical Data

Voltage

N/A 208 to 230 V

Number of Phases

N/A 1

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 6.9 A

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 2 A

Min. Circuit Ampacity

N/A 33.7/33.7 A

Max. Overcurrent Protection

N/A 50/50 A

Power Supply Conduit Hole Diameter

N/A 1.125 in

Low-Voltage Conduit Hole Diameter

N/A 0.5 in

Dimensions

Depth

N/A 74 in

Width

N/A 48-5/16 in

Height

N/A 39-7/8 in

Features and Benefits

N/A Installation
Daikin Packaged units are designed with an easier and faster installation in mind for both new construction and retrofit. Our packaged rooftop units are built to be a direct replacement for most rooftop units on the field without the need of a curb adapter, to be able to replace the unit in a shorter time and at a lower expense.

Cabinet Construction
Daikin packaged rooftop units are made with high quality galvanized steel with a powder-paint finish to provide higher corrosion resistance.

Compressor
High performance, low noise scroll compressors to match the required total load for efficient part load control.

Supply Fan
The direct drive with airfoil single width, single inlet (SWSI) Class II construction supply fan with aluminum fan +blades provides efficient and quiet operation at wide ranging static pressure and air flow requirements.

Coils
All units use large face area outdoor coils. These coils are constructed with seamless copper tubes, mechanically bonded into aluminum plate-type fins with full drawn collars to completely cover the tubes for high operating efficiencies.

Controls and Wiring
Packaged rooftop units come equipped with a well-organized, large, easy to use, weather proof internal control box with easy access, for a better user experience.

Filtration
Unit provides a draw-through filter section as standard for better air quality and longer lasting component maintenance.

Heating Section
Wide range of natural gas selections effectively handle most comfort heating demand from morning warm-up control to full heat, all available with Daikin’s Wrinkle Bend heat exchanger technology.

Gas Furnace
ETL certified heating modules provide a custom match to specific design requirement.

Electrical