Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
Multi Port Branch Selector Box - BSQ Series
VRV Accessories
Multi port branch selector box for use with VRV-IV heat recovery systems.
Daikin branch selector boxes provide ultimate flexibility when designing a heat recovery system. Mix and match single port branch selector boxes and multi port branch selector boxes on the same system to best suit the building.
- Available in 36 Mbh, 60 Mbh, and 96 Mbh capacities
- Available in 4, 6, 8, 10, and 12 ports
- Serve up to 54 Mbh per port
- Ultimate flexibility - mix and match single port and multi port branch selector boxes on the same system
- No limitation on the number of unused ports per box
- No condensate drain required
- 208-230V / 1Ph / 60 Hz
Unit of Measure
Items |
BS4Q54TVJ Multi Port Branch Selector Box - BSQ Series |
BS6Q54TVJ Multi Port Branch Selector Box - BSQ Series |
BS8Q54TVJ Multi Port Branch Selector Box - BSQ Series |
BS10Q54TVJ Multi Port Branch Selector Box - BSQ Series |
BS12Q54TVJ Multi Port Branch Selector Box - BSQ Series |
|||||
Model Type | N/A Branch Selector Box | |||||||||
Power Supply | N/A 208/230 V, 60 Hz, 1 phase | |||||||||
Number of Ports | N/A 4 | N/A 6 | N/A 8 | N/A 10 | N/A 12 | |||||
Maximum Capacity Index of Connectable Indoor Units | N/A 144 or less | N/A 216 or less | N/A 290 or less | N/A 290 or less | N/A 290 or less | |||||
Maximum Capacity Index of Connectable Indoor Units per Branch | N/A 54 or less | |||||||||
Maximum Number of Connectable Indoor Units | N/A 20 | N/A 30 | N/A 40 | N/A 41 | N/A 41 | |||||
Maximum Number of Connectable Indoor Units per Branch | N/A 5 | |||||||||
Number of Branches | N/A 4 | N/A 6 | N/A 8 | N/A 10 | N/A 12 | |||||
Casing | N/A Galvanized steel plate | |||||||||
Height | N/A 11-3/4 in298 mm | |||||||||
Width | N/A 14-9/16 in370 mm | N/A 22-13/16 in580 mm | N/A 22-13/16 in580 mm | N/A 32-5/16 in820 mm | N/A 32-5/16 in820 mm | |||||
Depth | N/A 18-15/16 in480 mm | |||||||||
Sound Absorbing Thermal Insulation Material | N/A Urethane foam, Polyethylene foam | |||||||||
Pipe Connections Indoor Unit - Liquid | N/A 1/4 in3/8 in | |||||||||
Pipe Connections Indoor Unit - Gas | N/A 1/2 in5/8 in | |||||||||
Pipe Connections Outdoor Unit - Liquid | N/A 3/8 in | N/A 1/2 in | N/A 1/2 in | N/A 5/8 in | N/A 5/8 in | |||||
Pipe Connections Outdoor Unit - Suction Gas | N/A 7/8 in | N/A 1 1/8 in | N/A 1 1/8 in | N/A 1 1/8 in | N/A 1 1/8 in | |||||
Pipe Connections Outdoor Unit - HP/LP Gas | N/A 3/4 in | N/A 3/4 in | N/A 3/4 in | N/A 1 1/8 in | N/A 1 1/8 in | |||||
Operating Sound Level | N/A 38 dBA | N/A 39 dBA | N/A 39 dBA | N/A 40 dBA | N/A 40 dBA | |||||
Max. Sound Level | N/A 45 dBA | N/A 47 dBA | N/A 47 dBA | N/A 48 dBA | N/A 48 dBA | |||||
Standard Accessories | N/A Accessory pipes, Clamps, Insulation tube, Vinyl tube, Installation manual | |||||||||
Weight | N/A 22 kg49 lb | N/A 31 kg68 lb | N/A 33 kg73 lb | N/A 46 kg101 lb | N/A 48 kg106 lb | |||||
|
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.