Print Back
Unit of Measure

Specifications

Compressor Type

N/A Scroll

Condenser Fan Motor Horsepower

N/A .167 hp

Frequency

N/A 60 Hz

Voltage

N/A 208-230 V

Cooling Capacity

N/A 34600 Btu/h

Heating Capacity

N/A 32800 Btu/h

Sound Level

N/A 74 dB

Compressor Rated Load Amps

N/A 11.6 A

Compressor Locked Rotor Amps

N/A 73 A

Condenser Fan Motor Full Load Amps

N/A 0.95 A

Valve Connection Type

N/A Sweat

Refrigerant Charge

N/A 112 oz

Shipped with Orifice Size

N/A 0.072 A

Phase

N/A 3

Minimum Circuit Ampacity

N/A 14.1 A

Maximum Overcurrent Protection

N/A 20 A

Min/Max Volts

N/A 197/253 V

Nominal Cooling Capacity (Tons)

N/A 3

Series

N/A DZ14S

Refrigerant Used

N/A R-410A

Shipping Weight

N/A 232 lb

Dimensions

Depth

N/A 29 in

Width

N/A 29 in

Height

N/A 32 1/4 in

Liquid Line Size O.D.

N/A 3/8 in

Suction Line Size O.D.

N/A 7/8 in

Liquid Valve Size O.D.

N/A 3/8 in

Suction Valve Size O.D.

N/A 3/4 in

Electrical Conduit Size

N/A 1/2 or 3/4 in

Parallel Unit Minimum Clearance

N/A 24 in

Unit Minimum Clearance

N/A 12 in

Unit Top Minimum Clearance

N/A 60 in

Lower Access Panel Depth

N/A 4 in

Lower Access Panel Height

N/A 17 in

Lower Access Panel Width

N/A 7 in

System Efficiency Metrics

System Performance SEER

N/A 14.0

Features

N/A Standard Features

  • R-410A chlorine-free refrigerant
  • Energy-efficient scroll compressor
  • Low-pressure switch
  • Liquid refrigerant return protection
  • Factory-installed, bi-flow liquid-line filter drier
  • Service valves with sweat connections and easy-access gauge ports
  • Copper tube/enhanced aluminum fin coil
  • Reliable time-initiated, temperatureterminated defrost control
  • Contactor with lug connection
  • Ground lug connection
  • Complies with ASHRAE Standard 90.1
  • AHRI Certified; ETL Listed
Cabinet Features
  • Innovative louvered sound control top design
  • Steel louver coil guard
  • Heavy-gauge galvanized-steel cabinet
  • Attractive Nickel Gray powder-paint finish
  • Top and side maintenance access
  • Service ports and controls are accessible while unit is operating
  • When properly anchored, meets the 2010 Florida Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)