Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
DRG Series - 3 to 6 ton
High efficiency gas/electric rooftop unit available with factory and field installed accessories for easy installation and serviceability
High efficiency gas/electric rooftop unit available with factory and field installed accessories for easy installation and serviceability
- Capacity range from 3 to 6 tons
- High efficiency direct drive ECM motor
- Aluminized wrinkle bend heat exchanger
Unit of Measure
Nominal Capacity |
N/A 5.0 TR |
Cooling Capacity |
N/A 60000 Btu/h |
Heating Capacity |
N/A 70000 Btu/h |
SEER |
N/A 17.1 |
EER |
N/A 13.0 |
Heat Range |
N/A Low |
No. of Burners |
N/A 3 |
Thermal Efficiency (T.E.) |
N/A 81 |
High Stage Temperature Rise Range |
N/A 25 to 55 ºF |
Low Stage Temperature Rise Range |
N/A 15 to 45 ºF |
Operating Weight |
N/A 655 lb |
Shipping Weight |
N/A 713 lb |
Height |
N/A 43 1/2 in |
Width |
N/A 48-5/16 in |
Depth |
N/A 74 in |
Motor Type |
N/A Direct Drive |
External Static Pressure (ESP) |
N/A Standard |
Wheel Dia. x Width |
N/A 12 x 11 in |
Indoor Nominal CFM |
N/A 2000 |
Evaporator Motor - RPM |
N/A 1300 |
Evaporator Motor Horsepower |
N/A 1.2 hp |
Filter Size |
N/A 14 X 20 X 2 (2) 20 X 20 X 2 (2) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 150 oz |
Evaporator Coil - Face Area |
N/A 9.2 ft² |
Evaporator Coil - Rows Deep |
N/A 4 |
Evaporator Coil - Fins per Inch |
N/A 16 |
Quantity of Condenser Fan Motors |
N/A 1 |
RPM (High/Low stage) |
N/A 750 / 1000 |
Outdoor Horsepower |
N/A 0.33 hp |
Diameter |
N/A 22 in |
No. of Fan Blades |
N/A 3 |
Condenser Coil Face Area |
N/A 19.0 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 28 |
Quantity |
N/A 1 |
Type |
N/A Scroll |
Stage |
N/A 2 |
Rated Load Amps |
N/A 5.3 A |
Locked Rotor Amps |
N/A 38.9 A |
Voltage |
N/A 575 V |
Number of Phases |
N/A 3 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 1.6 A |
Max External Static |
N/A 1 inWc |
Outdoor Fan FLA |
N/A 2.8 A |
Min. Circuit Ampacity |
N/A 11.1 A |
Max. Overcurrent Protection |
N/A 15 A |
Power Supply Conduit Hole Diameter |
N/A 1.125 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.5 in |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.