Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
- Capacity range from 3 to 12.5 tons
- Numerous voltages and phases for application flexibility
- All units has a choice of 3-phase 208/230V, 460V or 575V
- 3-5 ton units also have a choice of 1-phase 208/230V
- All models have ECM Direct-Drive Indoor Fan Motor
- Designed to fit standard curb sizes for ease of many replacements
Unit of Measure
Nominal Capacity |
N/A 7.5 TR |
Cooling Capacity |
N/A 90000 Btu/h |
Heating Capacity |
N/A 180000 / 145800 Btu/h |
IEER |
N/A 16 |
EER |
N/A 12.2 |
Heat Range |
N/A Medium |
No. of Burners |
N/A 6 |
Thermal Efficiency (T.E.) |
N/A 81 |
High Stage Temperature Rise Range |
N/A 25 to 55 ºF |
Low Stage Temperature Rise Range |
N/A 25 to 55 ºF |
Operating Weight |
N/A 1172 lb |
Shipping Weight |
N/A 1247 lb |
Height |
N/A 54-9/20 in |
Width |
N/A 60-3/16 in |
Depth |
N/A 93-5/8 in |
Motor Type |
N/A Direct Drive |
External Static Pressure (ESP) |
N/A 0.8 IN.W.G. |
Wheel Dia. x Width |
N/A 15.12 x 12.62 in |
Indoor Nominal CFM |
N/A 3000 |
Evaporator Motor - RPM |
N/A 1300 |
Evaporator Motor Horsepower |
N/A 2.4 hp |
Filter Size |
N/A 16x25x2 (4) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 140/133 oz |
Evaporator Coil - Face Area |
N/A 12.8 ft² |
Evaporator Coil - Rows Deep |
N/A 4 |
Evaporator Coil - Fins per Inch |
N/A 16 |
Quantity of Condenser Fan Motors |
N/A 2 |
RPM (High/Low stage) |
N/A 1050 |
Outdoor Horsepower |
N/A 0.33 hp |
Diameter |
N/A 22 in |
Condenser Coil Face Area |
N/A 35.3 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 28 |
Quantity |
N/A 2 |
Type |
N/A Scroll |
Stage |
N/A 1 |
Rated Load Amps |
N/A 4.4 A |
Locked Rotor Amps |
N/A 33 A |
Voltage |
N/A 575 V |
Number of Phases |
N/A 3 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 4.0 A |
Max External Static |
N/A 0.8 inWc |
Outdoor Fan FLA |
N/A 0.67 A |
Min. Circuit Ampacity |
N/A 15.1 A |
Max. Overcurrent Protection |
N/A 20 A |
Power Supply Conduit Hole Diameter |
N/A 1.375 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.375 in |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.