Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
Base efficiency Heat Pump rooftop unit available with field and factory installed accessories for easy installation and serviciability.
Unit of Measure
- Specifications
- Evaporator Motor / Coil
- Condenser Fan / Coil
- Compressor
- Electrical Data
- Dimensions
- Features
Cooling Capacity |
N/A 56500 Btu/h5 TR |
IEER |
N/A 14.0 |
EER |
N/A 11.5 |
Heating Capacity |
N/A 56500 Btu/h |
HSPF |
N/A 8 |
COP |
N/A 2.34 |
Sound Level |
N/A 76 dB |
Operating Weight |
N/A 632 lb |
Shipping Weight |
N/A 672 lb |
Motor Type |
N/A Direct Drive |
External Static Pressure (ESP) |
N/A Standard |
Wheel Dia. x Width |
N/A 12 x 11 in |
Indoor Nominal CFM |
N/A 1790 |
Evaporator Motor - RPM |
N/A 1200 |
Evaporator Motor Horsepower |
N/A 1.0 hp |
Filter Size |
N/A 14 x 20 x 2 (2) in20 x 20 x 2 (2) in |
Drain Size (NPT) |
N/A 3/4 in |
R410A Refrigerant Charge |
N/A 208 oz |
Evaporator Coil Face Area |
N/A 9.2 ft² |
Rows Deep |
N/A 4 |
Fins per Inch |
N/A 16 |
Outdoor Horsepower |
N/A 1 |
RPM (High/Low stage) |
N/A 1075 |
Outdoor Horsepower |
N/A 0.33 hp |
Diameter |
N/A 22 in |
No. of Fan Blades |
N/A 4 |
Condenser Coil Face Area |
N/A 19.0 ft² |
Rows Deep |
N/A 2 |
Fins per Inch |
N/A 16 |
Quantity |
N/A 1 |
Type |
N/A Scroll |
Stage |
N/A 1 |
Rated Load Amps |
N/A 25.0 A |
Locked Rotor Amps |
N/A 134.0 A |
Voltage |
N/A 208-230 V |
Number of Phases |
N/A 1 |
Frequency |
N/A 60 Hz |
Indoor Blower FLA |
N/A 6.9 A |
Max External Static |
N/A 0.8 inWc |
Outdoor Fan FLA |
N/A 2.3 A |
Min. Circuit Ampacity |
N/A 40.4 A |
Max. Overcurrent Protection |
N/A 60/60 A |
Power Supply Conduit Hole Diameter |
N/A 1.125 in |
Low-Voltage Conduit Hole Diameter |
N/A 0.5 in |
Depth |
N/A 74 in |
Width |
N/A 48-5/16 in |
Height |
N/A 43 1/2 in |
N/A
|