Base efficiency Heat Pump rooftop unit available with field and factory installed accessories for easy installation and serviciability.
Unit of Measure

Cooling Capacity

N/A 140000 Btu/h12-1/2 TR

IEER

N/A 11.6

EER

N/A 10.6

Heating Capacity

N/A 140000 Btu/h

COP at 47°F

N/A 3.30

COP at 17°F

N/A 2.25

Operating Weight

N/A 1314 lb

Shipping Weight

N/A 1394 lb

Motor Type

N/A Belt Drive

External Static Pressure (ESP)

N/A Standard

Wheel Dia. x Width

N/A 15 x 15 in

Indoor Nominal CFM

N/A 4250

Evaporator Motor - RPM

N/A 1165 1760

Evaporator Motor Horsepower

N/A 3.00 hp

Filter Size

N/A 25 x 25 x 2 (4) in

Drain Size (NPT)

N/A 3/4 in

R410A Refrigerant Charge

N/A 310/285 oz

Evaporator Coil Face Area

N/A 18.7 ft²

Rows Deep

N/A 4

Fins per Inch

N/A 16

Motor Sheave

N/A 1VP44X1-1/8

Blower Sheave

N/A AK84H

Belt

N/A AX51

Outdoor Horsepower

N/A 2

RPM (High/Low stage)

N/A 1075

Outdoor Horsepower

N/A 1/2 hp

Diameter

N/A 22 in

No. of Fan Blades

N/A 3

Condenser Coil Face Area

N/A 21.5 ft²

Rows Deep

N/A 3

Fins per Inch

N/A 16

Quantity

N/A 2

Type

N/A Scroll

Stage

N/A 1

Rated Load Amps

N/A 7.7 A

Locked Rotor Amps

N/A 54.0 A

Voltage

N/A 575 V

Number of Phases

N/A 3

Frequency

N/A 60 Hz

Indoor Blower FLA

N/A 3.5 A

Max External Static

N/A 0.8 inWc

Outdoor Fan FLA

N/A 1 A

Min. Circuit Ampacity

N/A 22.8 A

Max. Overcurrent Protection

N/A 30 A

Power Supply Conduit Hole Diameter

N/A 1.375 in

Low-Voltage Conduit Hole Diameter

N/A 0.375 in

Depth

N/A 93-3/4 in

Width

N/A 60-3/8 in

Height

N/A 58-3/5 in

N/A

  • Capacity Range from 7.5 to 12.5 tons
  • Belt Drive flexibility
  • Two stage capacity for partial load