Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.
CAD CART (0)
▾
Unit of Measure
Voltage |
N/A 208 to 230 V |
Frequency |
N/A 60 Hz |
Number of Phases |
N/A 1 |
Rated Capacity (Min. - Max.) - Cooling |
N/A 18000 (5100 - 18500) Btu/h |
Rated Capacity (Min. - Max.) - Heating |
N/A 20000 (5800 - 21200) Btu/h |
Running Current (Rated) - Cooling |
N/A 8.40 to 9.29 A |
Running Current (Rated) - Heating |
N/A 7.89 to 8.70 A |
Power Consumption (Rated) - Cooling |
N/A 1875 W |
Power Consumption (Rated) - Heating |
N/A 1755 W |
Power Factor (Rated) - Cooling |
N/A 97.0 % |
Power Factor (Rated) - Heating |
N/A 97.0 % |
Amount of Additional Charge of Refrigerant |
N/A 0.21 oz/ft20 g/m |
Color |
N/A White |
Airflow Rate (H) - Cooling |
N/A 350 ft³/min9.9 m³/min |
Airflow Rate (H) - Heating |
N/A 413 ft³/min11.7 m³/min |
Airflow Rate (M) - Cooling |
N/A 275 ft³/min7.8 m³/min |
Airflow Rate (M) - Heating |
N/A 332 ft³/min9.4 m³/min |
Airflow Rate (L) - Cooling |
N/A 226 ft³/min6.4 m³/min |
Airflow Rate (L) - Heating |
N/A 275 ft³/min7.8 m³/min |
Airflow Rate (SL) - Cooling |
N/A 208 ft³/min5.9 m³/min |
Airflow Rate (SL) - Heating |
N/A 208 ft³/min5.9 m³/min |
Air Direction Control |
N/A Right, Left, Horizontal, Downward |
Air Filter |
N/A Removable, Washable, Mildew Proof |
Temperature Control |
N/A Microcomputer Control |
Sound Pressure Level (H) - Cooling |
N/A 46 dBA |
Sound Pressure Level (H) - Heating |
N/A 47 dBA |
Sound Pressure Level (M) - Cooling |
N/A 40 dBA |
Sound Pressure Level (M) - Heating |
N/A 41 dBA |
Sound Pressure Level (L) - Cooling |
N/A 35 dBA |
Sound Pressure Level (L) - Heating |
N/A 35 dBA |
Sound Pressure Level (SL) - Cooling |
N/A 30 dBA |
Sound Pressure Level (SL) - Heating |
N/A 30 dBA |
Chargeless |
N/A 32-3/4 in10 m |
Weight |
N/A 12 kg27 lb |
Gross Weight |
N/A 15 kg33 lb |
System Performance SEER2/HSPF2 - Cooling |
N/A 14.50 |
System Performance SEER2/HSPF2 - Heating |
N/A 7.80 |
System Performance EER2 - Cooling |
N/A 9.60 Btu/h·W |
System Performance COP2 - Heating |
N/A 3.34 W/W |
Type |
N/A Cross Flow Fan |
Speed |
N/A 5 Steps, Quiet, Auto |
Running Current (Rated) - Cooling |
N/A 0.07 A |
Running Current (Rated) - Heating |
N/A 0.12 to 0.13 A |
Power Consumption (Rated) - Cooling |
N/A 28 W |
Power Consumption (Rated) - Heating |
N/A 42 W |
Power Factor (Rated) - Cooling |
N/A 96.1 - 87.0 % |
Power Factor (Rated) - Heating |
N/A 96.2 - 87.0 % |
Depth |
N/A 8-3/8 in212 mm |
Width |
N/A 39-5/16 in998 mm |
Height |
N/A 11-15/16 in303 mm |
Max. Interunit Piping Length |
N/A 98-1/2 in30 m |
Max. Interunit Height Difference |
N/A 65-5/8 in20 m |
Packaged Depth |
N/A 15-5/16 in389 mm |
Packaged Width |
N/A 43-3/8 in1101 mm |
Packaged Height |
N/A 12-11/16 in322 mm |
Pipe Connections - Liquid |
N/A 1/4 in6.4 mm |
Pipe Connections - Gas |
N/A 1/2 in12.7 mm |
Pipe Connections - Drain |
N/A 11/16 in18.0 mm |
Your access to and use of the Daikin web site is subject to the Terms and Conditions and all applicable laws.